Report ID: Sample Report / Client
Prepared For:
HouseMaster Client
Property Address:
12345 Sample Report
Phoenix AZ xxxxxx
Rogers & Kunnen Inc dba HouseMaster Home and Termite Inspections
Inspector: Harold J Kunnen
3030 S Rural Rd, STE #109
Tempe AZ 85282
480-345-8570
Inspection Date: 8/16/2010
(c) Copyright 2001-2008 HMA Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
 
Report ID: Sample Report / Client

Inspection Report Attachments
HouseMaster on Twitter, Facebook & YouTube

Sample Termite Report

(c) Copyright 2001-2008 HMA Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
 
Report ID: Sample Report / Client

Table of Contents


(c) Copyright 2001-2008 HMA Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
 
Report ID: Sample Report / Client
INSPECTION INFORMATION
CLIENT:
HouseMaster Client
PROPERTY ADDRESS:
12345 Sample Report
Phoenix AZ xxxxxx
INSPECTION DATE/TIME:
8/16/2010 - 09:02 AM
INSPECTOR:
Harold J Kunnen
INSPECTION COMPANY:
Rogers & Kunnen Inc dba HouseMaster Home and Termite Inspections
3030 S Rural Rd, STE #109
Tempe AZ 85282
480-345-8570
INSPECTION DETAILS
DESCRIPTION:
Single Family

AGE OF HOME:
6 to 7 years

TYPE OF INSPECTION:
Standard Home Inspection

PEOPLE PRESENT:


STATUS OF HOME:
Vacant

WEATHER:
Cloudy

TEMPERATURE:
80 F

ANCILLARY SERVICES:
Wood-Destroying Insect and WaterWorks Package

AUTHORIZED DISTRIBUTION:
Client and Client's Agent

BTR INSPECTOR LICENSE: #38065:
#38065

  
INTRODUCTION
The purpose of this report is to render the inspector's professional opinion of the condition of the inspected elements of the referenced property (dwelling or house) on the date of inspection. Such opinions are rendered based on the findings of a standard limited time/scope home inspection performed according to the Terms and Conditions of the Inspection Order Agreement and in a manner consistent with applicable home inspection industry standards.
The inspection was limited to the specified, readily visible and accessible installed major structural, mechanical and electrical elements (systems and components) of the house. The inspection does not represent a technically exhaustive evaluation and does not include any engineering, geological, design, environmental, biological, health-related or code compliance evaluations of the house or property. Furthermore, no representations are made with respect to any concealed, latent or future conditions.
The GENERAL INSPECTION LIMITATIONS on the following page provides information regarding home inspections, including various limitations and exclusions, as well as some specific information related to this property.
The information contained in this report was prepared exclusively for the named Clients and is not transferable without the expressed consent of the Company. The report, including all Addenda, should be reviewed in its entirety.
REPORT TERMINOLOGY
The following terminology may be used to report conditions observed during the inspection. Additional terms may also be used in the report:
SATISFACTORY - Element was functional at the time of inspection. Element was in working or operating order and its condition was at least sufficient for its minimum required function, although routine maintenance may be needed.
FAIR - Element was functional at time of inspection but has a probability of requiring repair, replacement or other remedial work at any time due to its age, condition, lack of maintenance or other factors. Have element regularly evaluated and anticipate the need to take action.
POOR - Element requires immediate repair, replacement, or other remedial work, or requires evaluation and/or servicing by a qualified specialist.
NOT APPLICABLE - All or individual listed elements were not present, were not observed, were outside the scope of the inspection, and/or were not inspected due to other factors, stated or otherwise.
NOT INSPECTED (NOT RATED) - Element was disconnected or de-energized, was not readily visible or accessible, presented unusual or unsafe conditions for inspection, was outside scope of the inspection, and/or was not inspected due to other factors, stated or otherwise. Independent inspection(s) may be required to evaluate element conditions. If any condition limited accessibility or otherwise impeded completion of aspects of the inspection, including those listed under LIMITATIONS, it is recommended that limiting factors be removed or eliminated and that an inspection of these elements be arranged and completed prior to closing.
IMPORTANT NOTE: All repair needs or recommendations for further evaluation should be addressed prior to closing. It is the client’s responsibility to perform a final inspection to determine the conditions of the dwelling and property at the time of closing. If any decision about the property or its purchase would be affected by any condition or the cost of any required or discretionary remedial work, further evaluation and/or contractor cost quotes should be obtained prior to making any such decisions.
NATURE OF THE FRANCHISE RELATIONSHIP
The Inspection Company ("Company") providing this inspection report is a franchisee of HMA Franchise Systems, Inc. ("Franchisor"). As a franchisee, the Company is an independently owned and operated business that has a license to use the HouseMaster names, marks, and certain methods. In retaining the Company to perform inspection services, the Client acknowledges that Franchisor does not control this Company’s day-to-day activities, is not involved in performing inspections or other services provided by the Company, and is in no way responsible for the Company’s actions. Questions on any issues or concerns should be directed to the listed Company.
GENERAL INSPECTION LIMITATIONS
CONSTRUCTION REGULATIONS - Building codes and construction standards vary regionally. A standard home inspection does not include evaluation of a property for compliance with building or health codes, zoning regulations or other local codes or ordinances. No assessments are made regarding acceptability or approval of any element or component by any agency, or compliance with any specific code or standard. Codes are revised on a periodic basis; consequently, existing structures generally do not meet current code standards, nor is such compliance usually required. Any questions regarding code compliance should be addressed to the appropriate local officials.
HOME MAINTENANCE - All homes require regular and preventive maintenance to maximize the economic life spans of elements and to minimize unanticipated repair or replacement needs. Annual maintenance costs may run 1 to 3% (or more) of the sales price of a house depending on age, design, and/or the degree of prior maintenance. Every homeowner should develop a preventive maintenance program and budget for normal maintenance and unexpected repair expenses. Remedial work should be performed by a specialist in the appropriate field following local requirements and best practices.
ENVIRONMENTAL AND MOLD ISSUES (AND EXCLUSIONS) - The potential health effects from exposure to many elements found in building materials or in the air, soil, water in and/or around any house are varied. A home inspection does not include the detection, identification or analysis of any such element or related concerns such as, but not limited to, mold, allergens, radon, formaldehyde, asbestos, lead, electromagnetic fields, carbon monoxide, insecticides, refrigerants, and fuel oils. Furthermore, no evaluations are performed to determine the effectiveness of any system designed to prevent or remove any elements (e.g., water filters or radon mitigation). An environmental health specialist should be contacted for evaluation of any potential health or environmental concerns. Review additional information on MOLD/MICROBIAL ELEMENTS below.
AESTHETIC CONSIDERATIONS - A standard building inspection does not include a determination of all potential concerns or conditions that may be present or occur in the future including aesthetic/cosmetic considerations or issues (appearances, surface flaws, finishes, furnishings, odors, etc.).
DESIGN AND ADEQUACY ISSUES - A standard home inspection does not include any element design or adequacy evaluations including seismic or high-wind concerns, soil bearing, energy efficiencies, or energy conservation measures. It also does not address in any way the function or suitability of floor plans or other design features. Furthermore, no determinations are made regarding product defects notices, safety recalls, or other similar manufacturer or public/private agency warnings related to any material or element that may be present in any house or on any property.
ESTIMATED AGES - Any age estimations represent the inspector's opinion as to the approximate age, and are provided for general guidance purposes only. Estimations may be based on numerous factors including, but not limited to, appearance and owner comment. Obtain independent verification if knowledge of the specific age of any element is desired or required. Age estimates are given in "years" unless noted.
DESIGN LIFE RANGE - These figures represent the typical economic service life range (in years) for elements of similar design, quality and type, as measured from the time of original construction or installation. Any stated design life is presented solely as a guide. It does not take into consideration abnormal, unknown, or discretionary factors, and is not a prediction of future service life.
ELEMENT DESCRIPTIONS - Any descriptions or representations of element material, type, design, size, dimensions, etc., are based primarily on visual observation of inspected or representative components. Owner comment, element labeling, listing data, and rudimentary measurements may also be considered in an effort to describe an element. However, there is no guarantee of the accuracy of any material or product descriptions listed in this report; other or additional materials may be present. Independent evaluations and/or testing should be arranged if verification of any element's makeup, design, or dimension is needed. Any questions arising from the use of any particular terminology or nomenclature in this report should be addressed prior to closing.
REMEDIAL WORK - Quotes should be obtained prior to closing from qualified (knowledgeable and licensed as required) specialists/contractors to determine actual repair/replacement costs for any element or condition requiring attention. Any cost estimates provided with a home inspection, whether oral or written, only represent an approximation of possible costs. Cost estimates do not reflect all possible remedial needs or costs for the property; latent concerns or consequential damage may exist. If the need for remedial work develops or is uncovered after the inspection, prior to performing any repairs contact the Inspection Company to arrange a re-inspection to assess conditions Aside from basic maintenance suitable for the average homeowner, all repairs or other remedial work should be performed by a specialist in the appropriate field following local requirements and best practices.
SELLER DISCLOSURE - This report is not a substitute for Seller Disclosure. A Property History Questionnaire form may be provided with this report to help obtain background information on the property in the event a full Seller Disclosure form is not available. The buyer should review this form and/or the Seller Disclosure with the owner prior to closing for clarification or resolution of any questionable items. A final buyer inspection of the house (prior to or at the time of closing) is also recommended.
WOOD-DESTROYING INSECTS/ORGANISMS - In areas subject to wood-destroying insect activity, it is advisable to obtain a current wood-destroying insect and organism report on the property from a qualified specialist, whether or not it is required by a lender. A standard home inspection does not include evaluation of the nature or status of any insect infestation, treatment, or hidden damage, nor does it cover issues related to other house pests or nuisances or subsequent damage.
ELEMENTS NOT INSPECTED - Any element or component not evaluated as part of this inspection should be inspected prior to closing. Either make arrangements with the appropriate tradesman or contact the Inspection Company to arrange an inspection when all elements are ready for inspection.
HOUSE ORIENTATION - Location descriptions/references are provided for general guidance only and represent orientations based on a view facing the front of the house from the outside. Any references using compass bearings are only approximations. If there are any questions, obtain clarification prior to closing.
CONDOMINIUMS - The Inspection of condominium/cooperative do not include exteriors/ typical common elements, unless otherwise noted. Contact the association/management for information on common element conditions, deeds, and maintenance responsibilities.
MOLD AND MICROBIAL ELEMENTS / EXCLUSIONS
The purpose and scope of a standard home inspection does not include the detection, identification or assessment of fungi and other biological contaminants, such as molds, mildew, wood-destroying fungi (decay), bacteria, viruses, pollens, animal dander, pet or vermin excretions, dust mites and other insects. These elements contain/carry microbial particles that can be allergenic, infectious or toxic to humans, especially individuals with asthma and other respiratory conditions or sensitivity to chemical or biological contaminants. Wood-destroying fungi, some molds, and other contaminants can also cause property damage. One particular biological contamination concern is mold. Molds are present everywhere. Any type of water leakage, moisture condition or moisture-related damage that exists over a period of time can lead to the growth of potentially harmful mold(s). The longer the condition(s) exists, the greater the probability of mold growth. There are many different types of molds; most molds do not create a health hazard, but others are toxic.
Indoor mold represents the greatest concern as it can affect air quality and the health of individuals exposed to it. Mold can be found in almost all homes. Factors such as the type of construction materials and methods, occupant lifestyles, and the amount of attention given to house maintenance also contribute to the potential for molds. Indoor mold contamination begins when spores produced by mold spread by air movement or other means to an area conducive to mold growth. Mold spores can be found in the air, carpeting, insulation, walls and ceilings of all buildings. But mold spores only develop into an active mold growth when exposed to moisture. The sources of moisture in a house are numerous and include water leakage or seepage from plumbing fixtures, appliances, roof openings, construction defects (e.g., EIFS wall coverings or missing flashing) and natural catastrophes like floods or hurricanes. Excessive humidity or condensation caused by faulty fuel-burning equipment, improper venting systems, and/or inadequate ventilation provisions are other sources of indoor moisture. By controlling leakage, humidity and indoor air quality, the potential for mold contamination can be reduced. To prevent the spread of mold, immediate remediation of any water leakage or moisture problems is critical. For information on mold testing or assessments, contact a qualified mold specialist.
Neither the evaluation of the presence or potential for mold growth, nor the identification of specific molds and their effects, fall within the scope of a standard home inspection. Accordingly, the Inspection Company assumes no responsibility or liability related to the discovery or presence of any molds, their removal, or the consequences whether property or health-related.
ADDITIONAL COMMENTS

Mechanical System Upgrade Needs - No evaluations are made as part of a standard home inspection regarding heating, ventilation, or air conditioning (HVAC) system design, system efficiency, adequacy, compliance with current energy standards or costs, and other factors that may be associated with the need to or desire to repair, replace, or upgrade any equipment. If new HVAC equipment is required or desired, now or in the future, in addition to costs associated with the purchase and installation of the equipment itself, there may be additional expenses related to structural alteration or air handler and distribution system replacement or alterations. For additional information on energy efficiency requirements contact (  www.doe.gov).

Pictures in Report - Any pictures (photographs, graphics, or images) included in or provided in conjunction with this Inspection Report generally portray overviews of certain elements, depict specific conditions or defects described in report comments, or are used for orientation purposes.  Pictures provided do not necessarily reflect all conditions or issues that need attention or may otherwise be a concern. The inclusion of any picture is not in anyway designed to highlight or diminish the significance or severity of any defect or condition, except as may be described in the Inspection Report. The report must be read in its entirety for pertinent information.

The inspection is being conducted in accordance with the STANDARDS OF PROFESSIONAL PRACTICE For Arizona Home Inspectors.  Cick to Review the AZ SOPP

(c) Copyright 2001 - 2008 HMA Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
The inspection of roofs and rooftop elements is limited to readily visible and accessible elements as listed herein; elements and areas concealed from view for any reason cannot be inspected.  This inspection does not include chimney flues and flue liners, or ancillary components or systems such as lightning protection, solar panels, and similar elements, unless specifically stated. Element descriptions are provided for general information purposes only; the verification of roofing materials, roof age, and/or compliance with manufacturer installation requirements is not within the scope of a standard home inspection. Issues related to roof or roofing conditions may also be covered under other headings in this report, including the ATTIC section.

ROOF COVERING 1:
Type: Steep Slope
Material: Concrete Tile
Location: House and Garage
Est. Age: 6 Years
Design Life: 40-60 Years
Insp. Method: Walked
Special Limitations: Roof Design and/or Height
ROOF COVERING 2:
Type: Flat/Minimal Slope
Material: Single Ply
Location: Rear
Est. Age: 6 Years
Design Life: 5-10 Years
Insp. Method: Walked
CHIMNEY 1:
N/A
SFPNANI 
    1.0 ROOF COVERING 1
Tile mortar is cracking.  Repair as needed

Trees should be trimmed away from the house to prevent damage.

    1.1 ROOF COVERING 2
Normal wear noted for age.
    1.2 EXPOSED FLASHING
    1.3 PLUMBING STACKS
    1.4 VENTILATION COVERS
    1.5 SKYLIGHT(S)
    1.6 RAIN GUTTERS / EAVESTROUGHS
    1.7 DOWNSPOUTS / ROOF DRAINS
    1.8 FASCIA / SOFFITS
    1.9 CHIMNEY
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
1.0 ROOF COVERING 1 Picture 1
1.0 ROOF COVERING 1 Picture 2
1.0 ROOF COVERING 1 Picture 3
1.1 ROOF COVERING 2 Picture 1
NOTE: All roofs have a finite life and will require replacement at some point. In the interim, the seals at all roof penetrations and flashings, and the watertightness of rooftop elements, should be checked periodically and repaired or maintained as required.  Any roof defect can result in leakage, mold, and subsequent damage.  Conditions such as hail damage or manufacturing defects or whether the proper nailing methods or underlayment were used are not readily detectible during a home inspection.  Gutters (eavestroughs) and downspouts (leaders) will require regular cleaning and maintenance.  All chimneys and vents should be checked periodically.  In general, fascia and soffit areas are not readily accessible for inspection; these components are prone to decay, insect, and pest damage, particularly with roof or gutter leakage.  If any roof deficiencies are reported, a qualified roofer or the appropriate specialist should be contacted to determine what remedial action is required.  If the roof inspection was restricted or limited due to roof height, weather conditions, or other factors, arrangements should be made to have the roof inspected by a qualified roofer, particularly if the roofing is older or its age is unknown.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Roof Systems - The watertightness of a roofing system is dependent on the proper installation of the roofing material and underlayment, its physical condition, and the proper function of all flashings (metal or other membrane installed at protrusions through the roof, such as vent pipes, skylights and valleys). While general roofing conditions were reported, this report is not a guarantee the roof is or will be watertight or leak free.
Inspection Limitations - The evaluation of a roof is primarily a visual assessment based on general roofing appearances. The verification of actual roofing materials, installation methods or roof age is generally not possible. Conditions such as hail damage or the lack of underlayment may not be readily detectible and may result in latent concerns. If the inspection was restricted to viewing from the ground and/or was affected by weather conditions or other limitations, a roofer's assessment would be advisable, particularly if the roofing is old or age is unknown.
Slate/Tile/Cement Roofs - The key to the watertightness and longevity for these types of roofs is annual inspection and repair of any loose, missing or damaged shingles. In many cases, repairs will provide reasonable serviceability; however, replacement may be needed based on cost factors. Some of the cementitious roofs are asbestos-containing. If left intact, there is usual minimal concern; if damaged or removed, fibers may be released; proper precautions must be followed and additional costs should be anticipated to address this concern.
Flat Roofs/Membranes - Due to the low or minimal slope of flat roofs, they are particularly prone to leakage due to improper installation, ponding or poor maintenance. They generally require more maintenance than sloped roofing and any deficiencies, even minor ones, should be attended to promptly. The membranes of certain type roofs, particularly built-up roofs with gravel cover, are not readily visible for inspection.
Roof Flashings/Seal - Initial or recurring roof leakage is often due to inadequate or damaged flashing. All flashings should be checked periodically or if leakage occurs. Repair or seal as needed.
Plumbing Vents/Stacks - The flashing/boot seal at plumbing vents are prone to leakage. All vent pipe flashings should be checked periodically and should be repaired and/or sealed as needed. Vent stacks must have adequate clearance from windows and other roof or wall openings or vents. Extending the vent may prevent detrimental conditions.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
Inspection of exterior elements is limited to readily visible and accessible  surfaces of the house envelope and connected appurtenances as listed herein; elements concealed from view by any means cannot be inspected.  All exterior elements are subject to the effects of long-term exposure and sudden damage from ongoing and ever-changing weather conditions.  Style and material descriptions are based on predominant/representative components and are provided for general information purposes only; specific types and/or material make-up material is not verified.  Neither the efficiency nor integrity of insulated window units can be determined. Furthermore, the presence/condition of accessories such as storms, screens, shutters, locks and other attachments or decorative items is not included, unless specifically noted.  Additional information on exterior elements, particularly windows/doors and the foundation may be provided under other headings in this report, including the INTERIOR and FOUNDATION/SUBSTRUCTURE sections.

SIDING:
Stucco
PORCHES/DECKS:
N/A
SPECIAL LIMITATIONS:
Vegetation Overgrowth
SFPNANI 
    2.0 SIDING and Flashing
Noted typical stucco cracks at door and window opening.  There are several drill holes and gouges that need general repair.  Repair as needed.

The pest control application cover needs to be securely attached. Recommend further review of treatment history.

    2.1 WINDOWS
    2.2 ENTRY DOORS
    2.3 STAIRS / STOOPS
    2.4 PORCH(ES)
    2.5 RAILINGS
    2.6 FOUNDATION COATING
Recommend trimming back vegetation in contact with the house.

Not all foundation is visible due to stucco built into the grade.
    2.7 ELECTRIC / GFCI
    2.8 EXTERIOR FAUCET(S)
Noted typical leakage from valve stem.  Repair as needed.

A backflow preventer/anti-siphon device is generally required for exterior faucets and lawn irrigation systems in this area to prevent possible contamination of the water supply condition. Add where needed.

Noted corrosion at the rear pool back flow preventer.  Repair as needed.(Picture 1)

S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
2.0 SIDING and Flashing Picture 1
2.0 SIDING and Flashing Picture 2
2.0 SIDING and Flashing Picture 3
2.0 SIDING and Flashing Picture 4
2.0 SIDING and Flashing Picture 5
2.6 FOUNDATION COATING Picture 1
2.8 EXTERIOR FAUCET(S) Picture 1
NOTE: All surfaces of the envelope of the house should be inspected at least semi-annually, and maintained as needed.  Any exterior element defect can result in leakage and/or subsequent damage.  Exterior wood elements and wood composites are particularly susceptible to water-related damage, including decay, insect infestation, and mold.  The use of proper treated lumber or alternative products may help minimize these concerns, but will not eliminate them altogether.  While some areas of decay or damage may be reported, additional areas of concern may exist, subsequently develop, or be  discovered during repair or maintenance work.  Should you wish advice on any new or uncovered area of deterioration, please contact the Inspection Company.  Periodic caulking/resealing of all gaps and joints will be required. Insulated window/door units are subject to seal failure, which could ultimately affect the transparency and/or function of the window.  Lead-based paints were commonly used on older homes; independent inspection is required if confirmation or a risk assessment is desired.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Wood Deterioration - Exterior wood elements are particularly susceptible to decay and insect damage. The use of treated lumber may help to minimize these concerns but will not eliminate them altogether. While we have attempted to identify readily apparent areas of decay, additional areas of concern may be identified as they occur, spread, or are discovered during repair or maintenance work. Should you wish advice on any new or uncovered area of deterioration, please contact our office. All exterior wood elements should be inspected at least annually; repair and/or refinish as needed.
Synthetic Stucco/EIFS - Some synthetic stucco includes products such as Exterior Insulation Finish Systems (EIFS). EIFS incorporates foam insulation panels, reinforcement mesh and a textured finish coating. Certain EIFS products and/or installation methods create conditions that are highly susceptible to moisture infiltration and subsequent mold growth and/or structural damage due to water infiltration at penetrations, joints, and roof terminations. A moisture intrusion evaluation by a specialist is recommended, as a precaution.
Siding/Wood Soil Clearance - Siding materials and wood components close to or in direct contact with soil or mulch are conducive to decay and/or wood destroying insect infestation. Whenever possible, at least six (6) inches of clearance should be provided above the soil. All areas in contact or close to the ground should be checked. Foam insulations or other foundation cover increase the potential for hidden damage due to moisture or insect concerns. All areas in contact or close to the ground should be checked. Where possible, contact with the ground should be corrected. Wood-soil contact, unprotected wood, and high moisture conditions promote decay and insect activity. Any conducive conditions should be eliminated, if possible, to minimize consequential damage or further infestation. Damaged components should be corrected/addressed properly.
Window/Door Seals - Replacement of insulated glass windows or doors is usually required to correct failed or defective vacuum seals. Fortunately, the insulation value is usually not significantly reduced. Replacement time frame may be discretionary; however, conditions will gradually worsen with time.
Windows and Doors - Storms, screens, safety glazing, locks and other attachments are generally not inspected unless otherwise noted. Comments on storms generally are limited to surface conditions; function and operation are not evaluated. An inventory of storms/screens should be taken to confirm desired coverage exists and/or storage locations.
Exterior Faucets - Exterior faucets that do not operate may be turned off, not connected, or, in cold weather, may be frozen. Consider all factors when concerns are indicated. The use of backflow preventers is advised, and in many areas now required, to prevent possible contamination of the water supply condition.
Exterior Electric - Due to weathering factors and the potential hazards of exterior wiring, precaution must be used for the installation and maintenance of electrical components. Any damaged components should be corrected immediately. Recommend adding Ground-Fault Circuit-Interrupter (GFCI) protection if not present. GFCI noted, however, test operation indicated unit malfunctioned or did not work properly. All exterior circuitry should be inspected by a qualified electrician.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
Inspection of site elements is primarily intended to address the condition of listed, readily visible and accessible elements immediately adjacent to or surrounding the house for conditions and issues that may have an impact on the house.  Elements and areas concealed from view for any reason cannot be inspected. Neither the inspection nor report includes any geological surveys, soil compaction surveys, ground testing, or evaluation of the effects of, or potential for, earth movement such as earthquakes, landslides, or sinking, rising or shifting for any reason.  Information on local soil conditions and issues should be obtained from local officials and/or a qualified specialist prior to closing.  In addition to the stated limitations on the inspection of site elements, a standard home inspection does not include evaluation of elements such as underground drainage systems, site lighting, irrigation systems, barbecues, sheds, detached structures, fencing, privacy walls, docks, seawalls, pools, spas and other recreational items.  Additional information related to site element conditions may be found under other headings in this report, including the FOUNDATION/SUBSTRUCTURE and WATER PENETRATION sections.

PATIOS and columns:
Type: Concrete
Enclosure: Roof Only
Location: Rear of House
Column type: Stucco over wood frame
WALKWAYS/DRIVEWAYS:
Walks: Concrete
Driveway: Concrete
RETAINING WALLS:
N/A
SPECIAL LIMITATIONS:
Vegetation
  
SFPNANI 
    3.0 PATIO(S) and columns
Noted sheetrock tape joints loosening in the ceiling. Repair as needed.
    3.1 WALKWAYS
    3.2 DRIVEWAY
    3.3 RETAINING WALL(S)
    3.4 GROUND SLOPE AT FOUNDATION
    3.5 SITE GRADING and vegetation
Keep vegetation clear of the siding and stem wall.

There are uneven areas in the backyard from missing plants. Recommend leveling to prevent tripping.

S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
3.0 PATIO(S) and columns Picture 1
3.0 PATIO(S) and columns Picture 2
NOTE:  Site conditions are subject to sudden change with exposure to rain, wind, temperature changes, and other climatic factors.  Roof drainage systems and site/foundation grading and drainage must be maintained to provide adequate water control.  Improper/inadequate grading or drainage and other sil/site factors can cause or contribute to foundation movement or failure, water infiltration into the house interior, and/or mold concerns. Independent evaluation by an engineer or soils specialist is required to evaluate geological or soil-related concerns.  Houses built on expansive clays or uncompacted fill, on hillsides, along bodies of water, or in low-lying areas are especially prone to structural concerns.  All improved surfaces such as patios, walks, and driveways must also be maintained to drain water away from the foundation.  Any reported or subsequently occurring deficiencies must be investigated and corrected to prevent recurring or escalating problems.  Independent evaluation of ancillary and site elements by qualified servicepersons is recommended prior to closing.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Site Elements - While informational comments may be made related to the condition of certain site elements, the primary intent of inspection of any site element is limited to evaluation relative to its effect on the building.
Geological Factors - This report does not include evaluation of any soils or geological conditions/concerns. Construction on certain soils, particularly expansive clays, fill soils, hillside and waterfront areas, necessitate special design consideration. Evaluation of these factors, or the need for them, is beyond the scope of this inspection. Pertinent information should be obtained from local officials and/or a qualified specialist prior to closing, particularly if any concerns are detected or if home is in a detrimental soils area.
Grading and Drainage - To reduce the amount of water run-off or possibility of water penetration and/or structural concerns, provide proper contouring (grading) along the foundation and where needed on the site. Houses on hills or in low-lying areas will be prone to drainage concerns. Improper/inadequate grading and/or drainage can cause/contribute to foundation movement and/or failure. Deficiencies must be corrected to prevent problems.
Site/Underground Drains - Site drains, including any underground piping and downspout drains, often must be regularly maintained/cleared in order to provide adequate water run-off and discharge. Adequacy of any such system cannot be readily determined.
Finished Surfaces - Spalling or cracking of concrete surfaces may not affect function provided no lateral displacement has occurred. Maintain as required or correct to eliminate any trip hazard that may exist or develop.
Grading Provisions - To reduce the amount of water run-off or ponding and potential for water penetration and/or structural concerns, a positive slope away from the foundation should be provided around the perimeter of the house. Maintenance of a suitable ground cover is also advised. Depressions or negatively graded areas should be corrected/improved to help direct any roof or surface run-off away from the foundation. The periodic addition of new fill soil and regarding may be required, especially with new homes. A negative grade slope can cause structural and/or water infiltration problems. Excessive soil/water pressures can actually cause lateral movement of the foundation, a potentially serious concern. Deficiencies must be corrected and suitable drainage conditions must be maintained in order to prevent problems.
Vegetation/Landscaping - The site vegetation and landscaping should be maintained to prevent damage to the structure. Carefully remove any overgrowth to check for damage.
Lawn Irrigation - Lawn Irrigation systems are not inspected within the scope of a standard home inspection. Advise evaluation prior to closing by a qualified contractor. Buried lines are subject to hidden damage or leakage. Seasonal maintenance will be required. Chronic spray from lawn sprinklers onto the house may cause structural damage, insect infestation or other problems. Entire system should be checked and corrected for orientation and spray pattern.
Pool/Spa - The inspection of pools/spas, including the integrity and watertightness of the shell/structure, is not part of a standard home inspection. Advise independent evaluation by a pool/spa specialist prior to closing.
Fencing/Sheds - The inspection of fencing, site walls, and sheds is not included in the scope of a standard home inspection. Wood components are prone to decay and insect damage. Advise a check of these elements for current conditions and assurance of personal acceptability.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
Inspection of the garage is limited to readily visible and accessible elements as listed herein.  Elements and areas concealed from view cannot be inspected.  More so than most other areas of a house, garages tend to be filled with storage and other items that restrict visibility and hide potential concerns, such as water damage or insect infestation.  A standard home inspection does not include an evaluation of the adequacy of the fire separation assemblies between the house and garage, or whether such assemblies comply with any specific requirements.  Inspection of garage doors with connected automatic door operator is limited to a check of operation utilizing hard-wired controls only.  Additional information related to garage elements and conditions may be found under other headings in this report, including ROOFS and EXTERIOR ELEMENTS.

GARAGE DESCRIPTION and fire separation:
Type: Two Car
Construction: Wood Frame
Finish at House: Drywall on Wall
Door at House: Solid Door w/ Self-closer
GARAGE ROOF:
Type: Moderate Slope
Material: Concrete Tile
Est. Age: 6 Years
Design Life: 40-60 Years
Insp. Method: Walked
Special Limitations: Roof Design and/or Height
GARAGE ATTIC:
Insp. Method: Limited Entry
Form: Indeterminate
Type: None
HOUSE/GARAGE WALL:
Finish at House: Drywall on Wall
Door at House: Solid Door w/ Self-closer
Insulation: Indeterminate - Wall Covered
Vapor Retarder: Indeterminate
SPECIAL LIMITATIONS:
Covered Framing
 
SFPNANI 
    4.0 ROOFING
Refer to roofing section.
    4.1 EXPOSED FRAMING
Framing is covered.
    4.2 FLOOR SLAB
THe slab is labeled post tension concrete.  Do not drill holes.
    4.3 FOUNDATION
Not all foundation is visible due to storage and cabinets.
    4.4 ATTIC VENTILATION
    4.5 WALLS / CEILINGS
Typical wear.
    4.6 SIDING
Normal Wear
    4.7 VEHICLE DOOR(S)
Recommend lubrication ... Noted noisy hinges.
    4.8 DOOR OPERATOR(S) and safety reverse
Normal wear.

Needs lubrication and service.
    4.9 ELECTRIC / GFCI
    4.10 HOUSE / SERVICE DOOR(S)
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
4.3 FOUNDATION Picture 1
4.3 FOUNDATION Picture 2
NOTE: Any areas obstructed at the time of inspection should be cleared and checked prior to closing.  The integrity of the fire-separation wall/ceiling assemblies generally required between the house and garage, including any house-to-garage doors and attic hatches, must be maintained for proper protection.  Review manufacturer use and safety instructions for garage doors and automatic door operators.  All doors and door operators should be tested and serviced on a regular basis to prevent personal injury or equipment damage. Any malfunctioning doors or door operators should be repaired prior to using. Door operators without auto-reverse capabilities should be repaired or upgraded for safety.  The storage of combustibles in a garage creates a potential hazard, including the possible ignition of vapors, and should be restricted.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Limitations/Obstructions - More than many other areas of a house, garages tend to contain storage and other items that restrict the ability to observe the structure and other components. Any noted limitation may be in addition to normal restrictions. Recommend all obstructed areas be inspected when clear.
Garage/House Separation - Fire-rated wall/ceiling assemblies are generally required between the house and garage. A home inspection generally does not address any specific requirement; rather fire-separation considerations are limited to a determination as to whether the frame walls are covered. Wall insulations and vapor retarders are generally not observable and may only be commented on if an observed defect exists. The integrity of any fire-separation assembly must be maintained for proper protection. Any gaps or openings should be covered/sealed with suitable materials. All joints must be taped.
Door Operator Function - In order to prevent personal injury or equipment damage, automatic door operators should stop and retract the door upon meeting reasonable resistance. This function should be checked on a regular basis and adjusted/corrected as needed. If the automatic door operator unit does not have retraction capabilities or doors not retract the door properly, it should be inspected by a qualified door specialist and repaired or upgraded as needed prior to future use.
Door Hardware/Mechanism - Damaged tracks, springs and cables may cause door operation malfunction but also represent potential safety hazards. A qualified specialist should inspect and repair any defective or missing components.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
The inspection of attic areas and the roof structure is limited to readily visible and accessible elements as listed herein.  Due to typical design and accessibility constraints such as insulation, storage, finished attic surfaces, roofing products, etc., many elements and areas, including major structural components, are often at least partially concealed from view and cannot be inspected.  A standard home inspection does not include an evaluation of the adequacy of the roof structure to support any load, the thermal value or energy efficiency of insulation, the integrity of vapor retarders, or the operation of thermostatically controlled fans.  Older homes generally do not meet insulation and energy conservation standards required for new homes.  Additional information related to attic elements and conditions may be found under other headings in this report, including ROOFS and INTERIOR ELEMENTS.

ATTIC:
Style: Indeterminate
Insp. Method: Inaccessible
ROOF CONSTRUCTION:
Framing: Wood Trusses
Deck: Wood Sheathing
Deck: Plywood
INSULATION:
Form: Indeterminate
Form: Blankett/Batt
Type: Fiberglass
Est. Average: 8+/- Inches
Vapor Retarder: Oberved in Areas/Extent Indeterminate
VENTILATION PROVISIONS:
Location: Rooftop
SPECIAL LIMITATIONS:
No Access
 
SFPNANI 
    5.0 ROOF FRAMING
There is no access to inspect attic space.
    5.1 ROOF DECK / SHEATHING
    5.2 VENTILATION PROVISIONS
    5.3 ATTIC VENTILATOR(S)
    5.4 WHOLE HOUSE FAN
    5.5 INSULATION
No access on the cathedral attic area of the house.
    5.6 ATTIC STAIRS
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
NOTE: Attic heat, moisture levels, and ventilation conditions are subject to change.  All attics should be monitored for any leakage, moisture buildup or other concerns.  Detrimental conditions should be corrected and ventilation provisions should be improved where needed.  Any comments on insulation levels and/or materials are for general information purposes only and were not verified.  Some insulation products may contain or release potentially hazardous or irritating materials--avoid disturbing.  A complete check of the attic should be made prior to closing after non-permanent limitations/obstructions are removed.  Any stains/leaks may be due to numerous factors; verification of the cause or status of all condition is not possible. Leakage can lead to mold concerns and structural damage. If concerns exist, recommend evaluation by a qualified roofer or the appropriate specialist. 

SUPPLEMENTAL INFORMATION - Review the additional details below.
Limitations/Obstructions - Due to typical design/accessibility constraints (insulation, storage, etc.,) evaluation of attic areas, including structural components, is generally limited. Any specifically noted limitations/obstructions are intended to highlight limitations beyond the norm. A complete check of the attic should be made when non-permanent limitations are removed.
Insulation - An energy assessment or audit is outside the scope of the standard home inspection. Any comments on amounts and/or materials are for general informational purposes only and were not verified. Some insulations may contain or release potentially hazardous materials; avoid disturbing. Wall insulation is not readily visible. Pre-1970s homes are more likely to have been constructed with insulation levels significantly below present day standards.
Ventilation/Vapor Retarders - Attic heat and moisture levels and ventilation adequacies are subject to change. Monitor for any significant buildup or changes and correct cause and/or improve ventilation as warranted. The presence and coverage adequacy of vapor retarders (barriers) cannot be confirmed in many cases.
Cathedral/Vaulted Ceiling - Cathedral/vaulted ceiling design restrictions generally prevent assessment of structural components, insulation or ventilation (moisture) provisions with this type construction. Ventilation inadequacies are common; assessment will be required when re-roofing or if any concerns are reported or develop.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
The inspection of bathrooms is limited to readily accessible and visible elements as listed herein.  Bathrooms are high-use areas containing many elements subject to ongoing wear and periodic malfunction, particularly fixtures and other components associated with the plumbing system.  Normal usage cannot be simulated during a standard home inspection.  Water flow and drainage evaluations are limited to a visual assessment of functional flow.  The function and watertightness of fixture overflows or other internal fixture components generally cannot be inspected.  A standard home inspection does not include evaluation of ancillary items such as saunas or steam baths.  Additional issues related to bathroom components may be found under other headings, including the PLUMBING SYSTEM.

BATHROOM ONE:
Description: Master Bath
Location: Master Bedroom
Ventilator(s): Exhaust Fan
BATHROOM TWO:
Description: Full Bath
Location: Hallway
Ventilator(s): Exhaust Fan
SPECIAL LIMITATIONS:
Hot Water is Off
SFPNANI 
    6.0 SINK(S)------------------------------------------------BATHROOM ONE
Shut off valves are stiff.  Use caution if you need to turn.

Hot water heater is turned off.  Could not verify hot water supply.  Recommend verifying hot water prior to closing.
    6.1 TOILET
    6.2 BATHTUB
Hot water is not on.  Recommend further review when the water heater is functioning.
    6.3 STALL SHOWER
Hot water is not on.  Recommend further review when the water heater is functioning.
    6.4 SURROUND / ENCLOSURE
    6.5 FLOOR(ING)
    6.6 WALLS / CEILING
    6.7 VENTILATOR
    6.8 ELECTRIC / GFCI
    6.9 SINK(S)---------------------------------------------------------BATHROOM TWO
Shut off valves are stiff.  Use caution if you need to turn.

Hot water heater is turned off.  Could not verify hot water supply.  Recommend verifying hot water prior to closing.
    6.10 TOILET
    6.11 BATHTUB
Normal wear.

Hot water heater is turned off.  Could not verify hot water supply.  Recommend verifying hot water prior to closing.
    6.12 STALL SHOWER
    6.13 FLOOR(ING)
    6.14 WALLS / CEILING
    6.15 VENTILATOR
    6.16 ELECTRIC / GFCI
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
NOTE:  Anticipate the possibility of leakage or other concerns developing with normal usage/aging or as concealed conditions are discovered with maintenance work or upon removal of carpeting, tile, shower enclosures, etc. The watertightness of all surfaces exposed to water must be maintained on a regular basis by caulking, grouting, or other means.  Hot water represents a potential scalding hazard; hot water supply temperatures should be maintained at a suitable level.  The water temperature at  fixtures, especially for showerings or bathing, generally will require additional  tempering for personal comfort and safety.  Due to the potential hazards associated with electric components located in bathroom areas, any identified concern should be addressed immediately. Ground-Fault Circuit-Interrupters (GFCIs) are recommended for all bathroom receptacle outlets.

SUPPLEMENTAL INFORMATION - Review the additional details below.
General Conditions - Bathrooms are high use areas with many components subject to periodic malfunction, particularly those related to the plumbing system. Normal usage could not be simulated during the inspection; therefore, anticipate the possibility of leakage or other concerns developing with normal usage/aging or as latent conditions are discovered with removal of carpeting, tile, shower pans, etc. The function and watertightness of fixture overflows or other internal fixture components generally cannot be assessed. The watertightness of all tile, enclosures, and other surfaces must be maintained on a regular basis.
Water Temperatures - The hot-water supply to all fixtures should be maintained at a safe temperature at all times. Water temperatures in excess of 120° F (49° C) generally represent a scalding hazard for most peoples; however, children and some adults are at risk of injury at even lower temperatures.
Drain Mechanisms - Minor repairs, adjustments or cleaning may correct many drain defects; however, tub drain mechanism repair may be problematic if there are access difficulties.
Caulking/Grouting - Caulking/grouting work is required to maintain watertightness of tilework and tub/shower enclosures. Check for substrate damage when surface damage or leakage is present.
GFCI Test - While a defective GFCI receptacle may still allow electricity to flow to the receptacle (and appliance), if the field test indicated any actual or suspected malfunction of a GFCI it should be corrected.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
Inspection of the kitchen is limited to visible and readily accessible elements as listed herein.  Elements concealed from view or not functional at the time of inspection cannot be inspected. The inspection of cabinetry is limited to functional unit conditions based on a representative sampling; finishes and hardware issues are not included. The inspection of appliances, if performed, is limited to a check of the operation of a basic representative cycle or mode and excludes evaluation of thermostatic controls, timing devices, energy efficiency considerations, cooking or cleaning adequacies, self-cleaning functions, the adequacy of any utility connections, compliance with manufacturer installation instructions, appliance accessories, and full appliance features (i.e., all cycles, modes, and controls).  Portable appliances or accessories such as washer, dryers, refrigerators, microwaves, and ice makers are generally excluded.  Additional information related to kitchen elements and appliances may be found under other headings in this report.

RANGE:
Electric Range
Estimated Age: 6 Years
DISHWASHER:
Estimated Age: 6 Years
DISPOSAL:
Estimated Age: 6 Years
VENTILATOR:
Exhaust Fan
Integral w/ Microwave
  
SFPNANI 
    7.0 PLUMBING / SINK
Shut-off valves are stiff.

RO Water purifier should be serviced periodically.

Hot water is not on.  Recommend further review when the water heater is functioning.

    7.1 FLOOR
    7.2 WALLS / CEILING
    7.3 ELECTRIC / GFCI
    7.4 RANGE
Normal wear.
    7.5 MICROWAVE
Normal wear.
    7.6 DISHWASHER
Normal wear.
    7.7 DISPOSAL
Disposal did not operate; Repair.
    7.8 VENTILATOR
Recommend sealing air leakage.  Much of the vented air is leaking back into the kitchen.  There may be something blocking the air flow to the installed ducting.  Repair.
    7.9 CABINETRY
    7.10 COUNTERTOP
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
7.0 PLUMBING / SINK Picture 1
7.7 DISPOSAL Picture 1
NOTE:  Many appliances typically have a high maintenance requirement and limited service life (5-12 years).  Operation of all appliances should be confirmed during a pre-closing inspection.  Obtain all operating instructions from the owner or manufacturer; have the homeowner demonstrate operation, if possible. Follow manufacturers' use and maintenance guidelines; periodically check all units for leakage or other malfunctions.  All cabinetry/countertops should also be checked prior to closing when clear of obstructions.  Utility provisions and connections, including water, waste, gas, and/or electric may require upgrading with new appliances, especially when a larger or upper-end appliance is installed.  Ground-Fault Circuit-Interrupters (GFCIs) are  recommended safety devices for all homes.  Any water leakage or operational defects should be addressed promptly; water leakage can lead to mold and hidden/structural damage.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Appliances - Appliance evaluations are outside the scope of a standard home inspection in many areas and are only inspected if so indicated. When performed, evaluations are limited to a basic operations check of only listed units and generally exclude thermostatic or timer controls, energy efficiency considerations, cooking or cleaning adequacies, appliance accessories, washer/dryers, refrigerators, ice makers and any portable appliances. Appliances typically have a 5-10 year service life. Operation of all appliances should be confirmed during a pre-closing inspection; have owner demonstrate operation if possible. Obtain all operating instructions from the owner or manufacturer.
Appliance Utilities - Appliance inspections do not include evaluation of the adequacy or capacity of any utility or utility connections or compliance with code or manufacturer requirements. Upgrades to water, waste, gas or electric lines may be required to meet specifications of any particular appliance; especially when a new or larger capacity appliance is added.
Microwaves - The evaluation of microwave units is not included in a standard inspection. The cooking adequacy of these units can vary. Follow manufacturer's guidelines; check periodically for leakage or other malfunctions.
Disposals - Any assessment of a garbage disposal is limited to a visual check of motor operation. No assessment of the unit's ability to grind/dispose of waste was made. This is a high maintenance item.
Compactors - Due to keyed controls and potential damage concerns, compactors often cannot be operated at the time of inspection. Recommend having owner demonstrate unit operation to confirm function.
Electric/GFCI - GFCIs are required in the kitchen and bathrooms of most newer houses; they are a recommended safety improvement for older houses.
GFCI Test - Ground-Fault Circuit-Interrupters (GFCIs) are required in the kitchens of most newer houses; they are a recommended safety improvement for older houses. Due to the high hazard potential of electric components in the kitchen area, any identified concern should be addressed immediately. While a defective GFCI receptacle may still allow electricity to flow to the receptacle (and appliance), if the field test indicated any actual or suspected malfunction of a GFCI it should be corrected.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
Inspection of the house interior is limited to readily accessible and visible elements as listed herein. Elements and areas that are inaccessible or concealed from view by any means cannot be inspected.  Aesthetic and cosmetic factors (e.g., paint and wallpaper) and the condition of finish materials and coverings are not addressed. Window and door evaluations are based on a random sampling of representative units. It is not possible to confirm safety glazing or the efficiency and integrity of insulated window/door units.  Auxiliary items such as security/safety systems (or the need for same), home entertainment or communication systems, structured wiring systems, doorbells, telephone lines, central vacuums, and similar components are not included in a standard home inspection.  Due to typical design restrictions, inspection of any fireplace, stove, or insert is limited to external conditions. Furthermore, such inspection addresses physical condition only; no code/fire safety compliance assessment or operational check of vent conditions is performed.  Additional information on interior elements may be provided under other headings in this report, including the FOUNDATION/SUBSTRUCTURE section and the major house systems.

PREDOMINANT WALLS & CEILINGS:
Wood Frame w/ Drywall
PREDOMINANT FLOORS:
Concrete Slab
w/ Carpeting and Tile
PREDOMINANT WINDOWS:
Sliders
w/Insulated Glass
w/Screens
FIREPLACES/STOVES:
N/A
DETECTORS:
Location: Hallway/Sleeping Area
Type: Battery Operated
Type: Hard-Wired
 
SFPNANI 
    8.0 CEILINGS
Normal wear.
    8.1 WALLS
Normal wear. Needs minor painting touchups.
    8.2 FLOORS (SLAB)
Covered areas are indirectly inspected.
    8.3 STAIRS
    8.4 RAILINGS
    8.5 WINDOWS
Normal wear.  Some windows are dirty.  Recommend further evaluation.
    8.6 ROOM DOORS
    8.7 SLIDER/PATIO DOORS
Screen door latch needs repair.
    8.8 DETECTOR TEST
    8.9 FIREPLACE
    8.10 FIREPLACE GAS BURNERS
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
8.7 SLIDER/PATIO DOORS Picture 1
NOTE: All homes are subject to indoor air quality concerns due to factors such as venting system defects, outgassing from construction materials, smoking, and the use of house and personal care products.  Air quality can also be adversely affected by the growth of molds, fungi and other micro-organisms as a result of leakage or high humidity conditions. If water leakage or moisture-related problems exist, potentially harmful contaminants may be present.  A home inspection does not include assessment of potential health or environmental contaminants or allergens. For air quality evaluations, a qualified testing firm should be contacted.  All homes experience some form of settlement due to construction practices, materials used, and other factors.  A pre-closing check of all windows, doors, and rooms when house is clear of furnishings, drapes, etc. is recommended. If the type of flooring or other finish materials that may be covered by finished surfaces or other items is a concern, conditions should be confirmed before closing. Lead-based paint may have been used in the painting of older homes. Chimney and fireplace flue inspections should be performed by a qualified specialist. Regular cleaning is recommended.  An assessment should be made of the need for and placement of detectors.  All smoke and carbon monoxide  detectors should be tested on a regular basis.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Structural Components - Evaluation of wall, ceiling or floor components is generally limited to readily visible structural conditions. Aesthetic or cosmetic factors, (e.g., paint, wallpaper) or the condition of finish materials or coverings are not considered unless specifically noted. Furthermore, it is not possible to determine the wall insulation, type or condition of surfaces or hidden structural concerns that may exist under floor cover, carpeting, paneling, drop ceilings, etc. If the type flooring is a concern, it should be confirmed before closing.
Indoor Air Quality/Mold - All houses are potentially subject to indoor air quality concerns due to numerous factors such as improper venting systems, outgassing from construction materials, etc. Air quality can also be adversely affected by the growth of molds, fungi and other micro-organisms—most are results of excess moisture conditions. A home inspection does not include assessment of potential health of environmental contaminants or allergens. If leakage occurs of detrimental moisture conditions exist or develop the possibility of potentially harmful contaminants exist and therefore should be immediately addressed. For air quality evaluations, a qualified testing firm should be contacted.
Windows and Doors - Windows and door evaluations are based on a random sampling of a representative number of units. All units should be checked by the buyer for possible operational concerns or other deficiencies. Unless noted, presence of safety glazing at windows/doors is not evaluated.
Insulated Glass - Insulated (double or triple glaze) windows and doors are subject to hard-to-detect failure of the airtight seal between panes. This failure can result in moisture and/or staining of the unit that can vary seasonally and increase with time. While actual/suspect seal failure may be noted, it is not within the scope of a standard inspection to assess the seal integrity of these type units. A pre-closing check of all units when house is clear of drapes, window coverings, etc. and the view of the windows is unobstructed is advised.
Infiltration/Leakage - The particular cause of a leak, or the status of any prior leakage conditions, cannot be readily verified in most cases. If any possible causes for leakage anywhere in the house are noted, it should be understood that additional unanticipated factors may also be contributing to or causing the condition. Hidden damage may exist. All areas of potential concern should be attended to and/or monitored for leakage. Any renovation or finish work should only start after verification and correction of the cause of leakage.
Smoke/CO Detectors - Smoke/fire detection systems and fire extinguishers are generally recommended for all houses, and may be required in some areas. Carbon monoxide and gas detectors are also recommended for houses with fuel-burning appliances, fireplaces or attached garages. Any installed systems should be checked/serviced at least monthly. The potential for elevated carbon monoxide levels exists in most houses, particularly if an attached garage of fuel burning units are present.
Window/Door Seals - Replacement of insulated glass windows or doors is usually required to correct failed or defective vacuum seals. Fortunately, the insulation value is usually not significantly reduced. Replacement time frame may be discretionary; however, conditions will gradually worsen with time.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client

The inspection of the house foundation/slab is limited to readily visible and access elements as listed herein. Most areas of a concrete house slabs are concealed from view due to foundation plantings, finished walls, high exterior grade lines, floor coverings, furnishings and other elements, and therefore cannot be inspected. Comments provided in this section only apply to the house slab; basement and garage slabs are typically covered in the respective report sections. Neither the inspection nor report includes geological surveys, soil compaction studies, ground testing, evaluation of the effects of or potential for earth movement such as earthquakes, landslides, or sinking, rising or shifting for any reason, or determination of prior flooding or water penetration. Furthermore, a standard home inspection is not a wood-destroying insect inspection, an engineering evaluation, a design analysis, or a structural adequacy study, including that related to high-wind or seismic restraint requirements.


FLOOR SLAB DESCRIPTION:
Whole House
Post-Tension Slab
SPECIAL LIMITATIONS:
Completely Covered by Floor Covering
Completely Covered by Tile/Carpeting
 
SFPNANI 
    9.0 SLAB EXTERIOR / EDGE
Not all foundation is visible due to landscape rock covering the stem wall.

Noted areas where vegetation covers the siding. Repair as needed.
    9.1 HOUSE FLOOR SLAB
Areas could not be observed to report on conditions due to floor coverings, furnishings, or other obstructions.
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
9.0 SLAB EXTERIOR / EDGE Picture 1
NOTE:  All foundations are subject to settlement and movement. Improper/inadequate grading or drainage can cause or contribute to foundation damage and/or failure and water penetration.  Deficiencies must be corrected and proper grading/drainage conditions must be maintained to minimize foundation and water penetration concerns.  If significant foundation movement or cracking is indicated, evaluation by an engineer or qualified foundation specialist is recommended.  All wood components are subject to decay and insect damage; a wood-destroying insect inspection is recommended.  Should decay and/or insect infestation or damage be reported, a full inspection should be made by a qualified specialist to determine the extent and remedial measures required. Insulation and other materials obstructing structural components are not normally moved or disturbed during a home inspection.  Obstructed elements or inaccessible areas should be inspected when limiting conditions are removed.  In high-wind or high-risk seismic areas, it would be advisable to arrange for an inspection of the house by a qualified specialist to determine whether applicable construction requirements are met or damage exists.  Should you seek advice or wish to arrange a new inspection for elements not visible during the  inspection, please contact the Inspection Company.

Even slab homes are subject to water penetration concerns.  It is not possible to accurately determine the extent of any past or current conditions or to predict future conditions or concerns. It is recommended that the homeowner be contacted for details about the nature of past and current water penetration and moisture-related conditions.  The homeowner and local authorities should also be questioned on the nature of any local flooding or water run-off conditions. Additional information related to the house structure or water penetration may be found under many other section headings in this report.


SUPPLEMENTAL INFORMATION - Review the additional details below.
WDI Treatment - If there are indications of prior treatment of the house for wood destroying insects, obtain documentation from owner on purpose and methods employed. No adequacy/contamination evaluations were performed.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
The inspection of the electric systems is limited to readily visible and access elements as listed herein.  Wiring and other components concealed from view for any reason cannot be inspected. The identification of inherent material defects or latent conditions is not possible.  The description of wiring and other components and the operational testing of electric devices and fixtures are based on a limited/random check of representative components.  Accordingly, it is not possible to identify every possible wiring material/type or all conditions and concerns that may be present. Inspection of Ground-Fault Circuit-Interrupters (GFCIs) is limited to the built-in test functions.  No assessment can be made of electric loads, system requirements or adequacy, circuit distribution, or accuracy of circuit labeling. Auxiliary items and electric elements (or the need for same) such as surge protectors, lighting protection systems, generators, security/safety systems, home entertainment and communication systems, structured wiring systems, low-voltage wiring, and site lighting are not included in a standard home inspection.  Additional information related to electric elements may be found under other many other headings in this report.

HOUSE SERVICE:
Service Line: Underground
Est. Service Capacity: 120/240 Volts; 200 Amps
Type Service Feeder: Copper
Est. Feeder Capacity: 200 Amps
SERVICE PANEL:
Type: Circuit Breaker
Main Disconnect: 200 Amps
Location: Exterior
DISTRIBUTION PANEL:
Type: Circuit Breaker Panel
Est. Capacity: 200 Amps
Main Disconnect: 200 Amps
Location: Exterior
SUBPANEL:
Type: Circuit Breaker Panel
Est. Capacity: 40 Amps
Location: Pool Equipment
PANEL CIRCUITS:
120 Volt Circuits: Copper Wire
240 Volt Circuits: Copper & Aluminum
CIRCUIT-INTERRUPTERS:
GFCI: In Panel
GFCI: At Receptacle Outlets
AFCI: Two Units Noted in Panel
SPECIAL LIMITATIONS:
Power Was Switched OFF/ON At The Main Disconnect
  
SFPNANI 
    10.0 SERVICE / ENTRANCE LINE
    10.1 SERVICE GROUNDING PROVISIONS
    10.2 MAIN DISCONNECT(S)
    10.3 DISTRIBUTION PANEL
    10.4 SUBPANEL(S)
Subpanel box is located at Pool area.
    10.5 DEVICES
The middle switch at the patio door needs repair to operate properly.

Outdoor outlet cover needs repair.

    10.6 WIRING / CONDUCTORS
The wiring for the spa has been partial removed.  Recommend further review and repair if a spa is added.(Picture 1)
    10.7 GFCI TEST
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
10.5 DEVICES Picture 1
10.5 DEVICES Picture 2
10.6 WIRING / CONDUCTORS Picture 1
NOTE:  Older electric service may be minimally sufficient or inadequate for present/future needs. Service line clearance from trees and other objects must be maintained to minimize the chance of storm damage and service disruption. The identification of inherent electric panel defects or latent conditions is not possible.  It is generally recommended that aluminum-wiring systems be checked by an electrician to confirm acceptability of all connections and to determine if any remedial measures are required. GFCIs are recommended for all high hazard areas (e.g., kitchens, bathrooms, garages and exteriors).  AFCIs are relatively new devices now required on certain circuits in new homes.  Consideration should be given to adding these devices in existing homes. The regular testing of GFCIs and AFCIs using the built-in test function is recommended. Recommend tracing and labeling of all circuits, or confirm current labeling is correct. Any electric defects or capacity or distribution concerns should be evaluated and/or corrected by a licensed electrician.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Electrical System - Evaluations and material descriptions are based on a limited/random check of components. Accordingly, it is not possible to identify every possible condition or concern in a standard inspection. All electric defects/potential concerns should be evaluated/corrected by a licensed electrician.
Panel/Circuit Wiring - Aluminum wiring is common on service feeders and major appliance circuits. All aluminum connections should be checked periodically. If household circuits are listed as aluminum wiring, review any inspector comments and general aluminum (120v) wiring comments. The operation or adaptability of any 240 volt dedicated appliance circuit for use with a particular appliance was not determined.
Ground-Fault Circuit Interrupters - GFCIs are designed to improve personal safety and are recommended for all houses. Regular testing of GFCIs is required to ensure proper operation and protection. In most areas GFCIs have only been required on certain circuits since the mid-1970s. It is recommended that GFCIs be installed in all high hazard areas (e.g., kitchens, bathrooms, garages and exteriors).
Arc-Fault Circuit Interrupters - As of January 1st, 2002 many areas required the installation of a safety device, known as an Arc-Fault Circuit-Interrupter (AFCI's), in new construction. The purpose of an AFCI is to reduce fire hazards associated with frayed wires and electric arcing, particularly in areas such as living rooms and bedrooms were corded fixtures are used. AFCI's are not be evaluated as part of a standard home inspection. If present, AFCI devices should be checked periodically. If not present consider upgrading for safety. Should an AFCI "trip," it should be left in the tripped" or "off" position, and arrangements should be made to have the circuit in question checked by a licensed electrician.
Service Disconnects - The absence of a single or sub-main disconnect generally does not effect system function but may be required and/or pose a potential safety hazard.
Panel Circuit Labeling - No determination was made of individual circuit distribution or accuracy of any circuit labeling. Recommend tracing and labeling, or confirm correct labeling, of all circuits.
Auxiliary/Low Voltage Systems - Evaluation of ancillary, low voltage electric or electronic equipment (e.g., TV, doorbell, computer, cable, lightning protection, surge protection, low voltage lighting, intercoms, site lighting, alarms etc.,) is not performed as part of a standard home inspection.
House Service Line - The service line must have adequate clearance above the ground and from other objects (trees, poles, etc.) and must be maintained in a weathertight condition.
GFCI Test - While a defective GFCI receptacle may still allow electricity to flow to the receptacle (and appliance), if the field test indicated any actual or suspected malfunction of a GFCI, it should be corrected.
System Ground - All systems require a ground rod or other suitable grounding provision including a jumper over any water meter. Questionable grounding provisions should be checked/confirmed.
Light Fixtures/Switches - Light fixtures, ceiling fans, etc., are generally randomly checked to assess basic wiring conditions. Any inoperative unit may be due to a defective fixture or bulb, connection to undetected switch or other factors.
Site Lighting/Wiring - Advise check of all site lighting components to ensure proper wiring procedures/operation.
Concealed Electric - Due to house design, aside from electric devices and fixtures visible within the house, all electric system components are concealed and therefore could not be inspected.  While it may be difficult to fully assess electric system conditions without opening walls or other destructive measures, an inspection and evaluation by a licensed electrician is recommended as a precautionary measure.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
The inspection of cooling systems (air conditioning and heat pumps) is limited to readily visible and accessible elements as listed herein.  Elements concealed from view or not functional for any reason cannot be inspected. A standard home inspection does not include a heat gain analysis, cooling design or adequacy evaluation, energy efficiency assessment, installation compliance check, or refrigerant issues.  Furthermore, portable units or add-on components such as electronic air cleaners are not inspected, unless specifically indicated.  The functional check of cooling systems is limited to the operation of a basic cycle or mode and excludes the evaluation of thermostatic controls, timing devices, analysis of distribution system flow or temperatures, or operation of full system features (i.e., all cycles, modes, and controls).  Air conditioning systems are not checked in cold weather.  Additional information related to the cooling system may be found under other headings in this report, including the HEATING SYSTEM section.

AIR CONDITIONING SYSTEM 1:
Brand: Carrier
Type: Electric Central Split
Est. Age: 6 Years
Design Life: 7-10 Years
Distribution: Ducted w/ Registers
Location: Attic
Location: Outside
  
SFPNANI 
    11.0 COOLING SYSTEM--COOLING SYSTEM 1
27.6 RLA 82-64=18 deg temp diff.  Recommend annual service to maintain performance.  Normal readings should be between 16  to 24 deg temp diff..
    11.1 OUTDOOR UNIT WITH SAFETY SHUT OFFS
Weather worn.

Recommend cleaning the coil inside the A/C cabinet periodically due to over grown vegetation.
    11.2 INDOOR BLOWER and Filter
    11.3 CONDENSATE PROVISIONS
    11.4 DUCTWORK and supply vents to each room
    11.5 THERMOSTAT
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
NOTE:  Regular cooling system maintenance is important. The older the unit the greater the probability of system deficiencies or failure. Inadequate cooling or other system problems may not be due simply to an inadequate refrigerant charge, as more significant concerns may exist.  Condensate lines and pumps, if present, should be checked regularly for proper flow; backup or leakage can lead to mold growth and structural damage.  All condensate drains must be properly discharged to the exterior or a suitable drain using an air gap. Cooling comfort will vary throughout most houses due to house or system design or other factors.  Filters need to be replaced/cleaned on a regular basis; periodic duct cleaning may also be required. Cooling systems cannot be safely or properly evaluated at low exterior temperatures. Arrange for an inspection when temperatures are at moderate levels for several days. Servicing or repair of cooling systems should be made by a qualified specialist.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Central Cooling - Evaluations are usually restricted to the basic operation of electric central air conditioning and heat pump systems. No heat gain, sizing, or design evaluations were performed. Thermostat calibration, accuracy and adequacy of conditioned air distribution were not determined. The evaporator coil (indoor coil) is not visible for inspection. Cool/cold weather operation/evaluation is not part of a standard inspection. No assessment was made related to the use of or potential hazards of any system refrigerant.
Heat Pumps - Heat pumps are designed to operate all year to provide cooling and heating. Most heat pumps have supplemental heating systems for cold weather (<40° F or 5° C). Due to design, anticipate low air flow/temperatures from registers. Also review pertinent HEATING SYSTEM comments. Identification of the presence of a heat pump unit (versus Central Cooling) is sometimes difficult; no verification of system type is made as part of the standard inspection.
Maintenance/Service - Regular cooling system maintenance is important. Due to the numerous causes of any system malfunction, assessment by a qualified cooling serviceman is advisable. Periodic refrigerant recharging may be needed; such conditions may not be predictable. Condensate back up or leakage can lead to mold growth.
Outdoor Unit - The outdoor unit base should be maintained in a reasonably level position. The coils will require periodic cleaning; clearance from vegetation/obstructions should also be provided.
Condensate Removal - All condensate must be properly discharged to the exterior or a suitable drain with an air gap. Condensate lines and pumps, if present, should be checked for proper flow regularly.
Blower/Filters) - Missing or clogged filters can affect system operation and possibly reduce the service life of the unit. Replace/clean filters when needed. Ductwork/blower cleaning may also be required periodically, particularly if the unit was operated without a filter.
Distribution System - Due to system design, balancing methods or other factors, airflow and/or supply provisions to areas appear limited/uneven. Improve as required or desired. Anticipate heat stratification.
Ceiling Fans - No determination is made regarding ceiling fan mounting adequacy, wiring methods, or product recall status as part of a standard inspection. As with other electric fixtures, fan evaluation is limited to assessment of basic electric supply. All fans should be checked for the potential concerns noted above.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
The inspection of heating systems is limited to readily visible and accessible elements as listed herein.  Elements concealed from view or not functional at the time of inspection for any reason cannot be inspected. A standard home inspection does not include a heat-loss analysis, heating design or adequacy evaluation, energy efficiency assessment, installation compliance check, chimney flue inspection or draft test, solar system inspection, or buried fuel tank inspection.  Furthermore, portable units and system accessories or add-on components such electronic air cleaners, humidifiers, and water treatment systems are not inspected, unless specifically indicated.  The functional check of heating systems is limited to the operation of a basic cycle or mode and excludes the evaluation of thermostatic controls, timing devices, analysis of distribution system flow or temperatures, or operation of full system features (i.e., all cycles, modes, and controls).  Additional information related to the heating system may be found under other headings in this report, including the COOLING SYSTEM section.

HEATING SYSTEM 1:
Type: Furnace
Brand: Carrier
Fuel: Natural Gas
Location: Attic
Est. Age: 6 Years
Design Life: 10-15 Years
Distribution: Ducted w/ Registers
SPECIAL LIMITATIONS:
Power Off/On Vacant House
 
SFPNANI 
    12.0 HEATING UNIT--SYSTEM 1
    12.1 BURNER
    12.2 FUEL LINE AT UNIT AND SAFETY SHUT OFFS
    12.3 VENT CONNECTOR
    12.4 BLOWER and filters
    12.5 DISTRIBUTION SYSTEM and supply vent to each room
    12.6 THERMOSTAT
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
NOTE:  Regular heating system maintenance is important.  The older the unit the greater the probability of system deficiencies or failure.  Combustion air provisions, clearances to combustibles, and venting system integrity must be maintained for safe operation.  Any actual or potential concerns require immediate attention, as health and safety hazards may exist, including the potential for carbon monoxide poisoning.  A thorough inspection of heat exchangers by a qualified heating specialist is recommended to determine heat exchanger conditions, particularly if the unit is beyond 5+ years old or any wear is indicated.  Heating comfort will vary throughout most houses due to house or system design or other factors.  Filters need to be replaced/cleaned on a regular basis; periodic duct cleaning may be required. Insulation on older heating systems may contain asbestos. Independent evaluation is required to address any possible asbestos or buried fuel tank concerns.  Servicing or repair of heating systems should be made by a qualified specialist.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Central Heating Systems - Evaluation is limited to an operational check of conventional residential systems. No design or heating adequacy evaluation, thermostat calibration assessment, heat loss analyses or active/passive solar systems evaluations are performed as part of a standard inspection. Furthermore, no specific evaluations were performed related to the presence of any fuel storage tanks or asbestos-containing materials. Independent evaluation is required to address any possible asbestos or tank concerns.
Hot Air Furnace - The heart of a furnace is a metal chamber referred to as a heat exchanger. All or most areas of this exchanger are not readily accessible or visible to a home inspector. Therefore, assessment of a furnace is limited to external and operational conditions. The older the unit, the greater the probability of failure. A thorough inspection by a qualified HVAC contractor is advised for full evaluation of heat exchanger conditions, particularly if the unit is beyond 5+ years old or any wear is exhibited. Check filters monthly; replace/clean as needed.
Heat Pumps - A heat pump is designed to operate all year to provide cooling and heating. Most heat pumps have supplemental heating systems for cold weather (< 40° F or 5° C). Due to design, anticipate low airflow/temperatures from registers. Also review pertinent HEATING SYSTEM comments. Identification of the presence of a heat pump unit (versus Central Cooling) is sometimes difficult; no verification of system type is made as part of the standard inspection.
Maintenance/Service - Servicing or repair of the heating system normally must be done by a qualified service company; most utility companies only service/handle gas supply concerns.
Blower/Filters) - Missing or clogged filters can affect system operation and possibly reduce the service life of the unit. Replace/clean filters as needed. Ductwork/blower cleaning may also be required periodically, particularly if the unit was operated without a filter.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
The inspection of the plumbing system is limited to readily visible and accessible elements as listed herein.  Piping and other components concealed from view for any reason cannot be inspected.  Material descriptions are based on a limited/random check of representative components.  Accordingly, it is not possible to identify every piping or plumbing system material, or all conditions or concerns that may be present.  A standard home inspection does not include verification of the type water supply or waste disposal, analysis of water supply quantity or quality, inspection of private onsite water supply or sewage (waster disposal) systems, assessment/analysis of lead piping/solder or lead-in-water concerns, or a leakage test of gas/fuel piping or storage systems. Furthermore, the function and effectiveness of any shut-off/control valves, water filtration or treatment equipment, irrigation/fire sprinkler systems, outdoor/underground piping, backflow preventers (anti-siphon devices), laundry standpipes, vent pipes, floor drains, fixture overflows, and similar features generally are not evaluated.  Additional information related to plumbing elements may be found under other headings in this report, including BATHROOMS and KITCHEN.

WATER SUPPLY PIPING:
Copper Where Visible
Cross-linked Poly (PEX)
DRAIN/WASTE LINES:
Plastic
Plastic (PVC/ABS)
LOCATION OF SHUT-OFFS:
Water: At Meter
Water: At Left Side of House
Gas: At Meter
WATER TREATMENT SYSTEM:
Water Softener
SPECIAL LIMITATIONS:
Vacant House
 
SFPNANI 
    13.0 WATER SUPPLY PIPING
PEX Plastic piping noted in the garage attic area.  Certain types of plastic piping systems have exhibited material or installation deficiencies resulting in premature leakage, particularly polybutylene (PB) piping manufactured prior to the mid 1990s. Some PB piping that developed leaks qualified for a special PB pipe repair program administered by the Consumer Plumbing Recovery Center or other group.  Some other settlement programs were also established.  Any problems that develop in newer systems may qualify for remedial work under manufacturer warranties. Contact the CPRC, the pipe manufacturer, or a qualified plumber or for assessment of the system and possible remedies if any prior concerns were reported or ongoing concerns exist(Picture 4).

Recommend periodic service of water softener system.  Repair corroded connection as needed.(Picture 3)

    13.1 WATER FUNCTIONAL FLOW AT FIXTURES
    13.2 DRAIN / WASTE PIPING FUNCTIONAL FLOW
    13.3 FIXTURE DRAINAGE
    13.4 EXTERIOR FAUCET(S)
Noted typical leaking at valve stem.


May need repair at the pool leveler and corroded shut off valve.

A backflow preventer/anti-siphon device is generally required for exterior faucets and lawn irrigation systems in this area to prevent possible contamination of the water supply condition. Add where needed.

    13.5 LAUNDRY AREA AND VENT FAN and dryer vent
Normal wear.

The vent fan is installed

    13.6 GAS PIPING
Gas shut off is located at the meter.
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
13.0 WATER SUPPLY PIPING Picture 1
13.0 WATER SUPPLY PIPING Picture 2
13.0 WATER SUPPLY PIPING Picture 3
13.0 WATER SUPPLY PIPING Picture 4
13.5 LAUNDRY AREA AND VENT FAN and dryer vent Picture 1
13.6 GAS PIPING Picture 1
NOTE:  Recommend obtaining documentation/verification on the type water supply and waste disposal systems.  If private onsite water and/or sewage systems are reported/determined to exists, independent evaluation (including water analyses) is recommended.  Plumbing systems are subject to unpredictable change, particularly as they age (e.g., leaks may develop, water flow may drop, or drains may become blocked).  Plumbing system leakage can cause or contribute to mold and/or structural concerns.  Some piping may be subject to premature failure due to inherent material deficiencies or water quality problems, (e.g., polybutylene pipe may leak at joints, copper water pipe may corrode due to acidic water, or old galvanized pipe may clog due to water mineral content).  Periodic cleaning of drain lines, including underground pipes will be necessary.  Periodic water analyses are recommended to determine if water filtration and treatment systems are needed.  Confirm and label gas and water shut-off valve locations.  A qualified plumber should perform all plumbing system repairs.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Water Supply/Waste Disposal - Neither the source, type nor quality of water supply, nor the method of waste disposal is determined as part of a standard home inspection. Advise obtaining documentation/verification of type systems. If a private water and/or waste system exists, independent evaluation by a specialist is recommended.
Plumbing Components - Evaluation of the plumbing system was limited to permanently connected fixtures and readily visible pipe conditions. The function and effectiveness of laundry standpipes, vent pipes, floor drains, fixture overflows, anti-siphon devices and similar items generally cannot be evaluated. Conditions are subject to unpredictable change, e.g., leaks may develop, water flow may drop, drains may become blocked, etc. The detection of sewer gases and the condition/function of sub-slab or in-ground piping is excluded from a standard inspection. In-ground piping is subject to blockage/collapse.
Shut Off/Location - Confirm and label gas and water shut-off valve locations. Provide full access at all times.
Plastic Piping - Certain types of plastic piping systems have exhibited material or installation deficiencies resulting in premature leakage, particularly polybutylene (PB) piping manufactured prior to the mid 1990s. Some PB piping that developed leaks qualified for a special PB pipe repair program administered by the Consumer Plumbing Recovery Center or other group.  Some other settlement programs were also established.  Any problems that develop in newer systems may qualify for remedial work under manufacturer warranties. Contact the CPRC, the pipe manufacturer, or a qualified plumber or for assessment of the system and possible remedies if any prior concerns were reported or ongoing concerns exist.
Backflow Preventer - These device are required in many areas, on exterior hose bibs (faucets) and at other threaded faucets such as laundry sinks to prevent water supply contamination.
Concealed Plumbing - Due to building/unit design, aside from plumbing fixtures visible within the dwelling, all plumbing system components are concealed and therefore could not be inspected. 

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
The inspection of hot water supply systems is limited to readily visible and accessible elements as listed herein.  Elements concealed from view for any reason cannot be inspected.  All standard water heaters require temperature-pressure relief valves (TPRV); these units are not operated during a standard home inspection but should be checked regularly for proper operation. A standard home inspection does not include evaluation of the adequacy/capacity of hot water supply systems, or inspection of saunas, steam baths, or solar systems. An increase in the hot water supply system capacity may be needed for large jetted baths or other fixtures requiring a large volume of hot water, or when bathroom or plumbing facilities are added or upgraded. Additional information related to the hot water supply system may be found under other headings in this report, including the BATHROOMS and PLUMBING SYSTEM sections.

HOT WATER SUPPLY 1:
Type: Direct-heated Tank
Brand: Bradford White
Est. 5o Gal.
Est. Age: 6 Years
Design Life: 7-10 Years
Location: Garage
SPECIAL LIMITATIONS:
Water and Power Turned Off/ON - Vacant House
 
SFPNANI 
    14.0 WATER HEATER SYSTEM 1
Normal wear. 

Gas is turned off at the control valve. Recommend service company verifying safe operation when gas is turned on.(Picture 2)

    14.1 VENT CONNECTOR
    14.2 GAS / FUEL LINES AT UNIT
    14.3 SAFETY VALVE PROVISIONS
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
14.0 WATER HEATER SYSTEM 1 Picture 1
14.0 WATER HEATER SYSTEM 1 Picture 2
NOTE: Maintaining hot-water supply temperatures at no more that about 120° F (49° C) for will reduce the risk of injury; hot water represents a potential scalding hazard. Anti-scald devices are available as an added safety measure. The combustion chamber or ignition sources of water heaters and other mechanical equipment in garage areas should be positioned/maintained at least 18 inches above the floor for safety reasons. Adequate clearance to combustibles must also be maintained around the unit and any vents. Restraining straps are generally required on heaters in active seismic zones. Safety valve (TPRV) discharge should be through a drain line to a readily visible area that can be monitored. Newer tanks should be drained periodically, but many old tanks are best left alone. Tankless or boiler coils systems have little or no storage capacity; a supplemental storage tank can often be added if needed. A qualified plumber or specialist should perform all water heating system repairs.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Domestic Hot Water - The adequacy of the domestic hot water supply or temperatures was not determined. Evaluations are limited to assessment of visual conditions and confirmation of heated water flow to the fixtures. Newer tanks should be drained periodically, but many old tanks are best left alone.
Dip Tubes - The dip tube is located in the water heater to direct incoming cold water to the bottom of the tank. Due to a manufacture defect, plastic dip tubes used in many tanks manufactured in 1993-1996 are subject to premature failure. To confirm possible coverage for replacement costs or consequential damage, contact a local plumber or the water heater manufacturer.
Relief Valves - All standard water heaters require temperature-pressure relief valves (TPRV). These units are not operated during a standard home inspection but should be checked regularly for proper operation.
Water Temperatures - Hot water temperature generally should not exceed approximately 120° F (49° C)at any fixture. Elevated temperatures should be corrected. Monitor and adjust as required. Anti-scald devices are available as a safety measure.
TPRV Discharge - Valve discharge should be through a drain line to a readily visible area so that it can be monitored. The lines should not be reduced below valve opening size (3/4 inch), or restricted in any way. Metal piping is recommended for the drain line; if plastic is allowed, only high temperature plastic is acceptable.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
Pool inspections are not part of a standard home inspection. When provided as an ancillary service, the inspection of pools is limited to readily visible and accessible elements as listed herein. Elements below the water line or otherwise concealed from view cannot be inspected. The inspection does not include testing of the electrical bonding system, the chemical composition or quality of the water, or internal filter conditions and filtering adequacy. A full inspection for structural damage and/or leakage is not possible without continual observation and/or drainage of the pool. There are special health and safety risks associated with the presence and use of pools; all homeowners should be aware of these risks.

DESCRIPTION:
In-Ground
LINER/SURFACE:
Concrete/Gunite
ESTIMATED AGE:
5 to 10 years
DESIGN LIFE:
20 to 25 Years
SPECIAL LIMITATIONS:
Vegetation
 
SFPNANI 
    15.0 DECK OR PATIO AT POOL
    15.1 INTERIOR FINISH/LINER
    15.2 COPING / EDGING
Noted mineral deposits which should be cleaned.
    15.3 TILEWORK / GROUTING
Noted mineral build up on the surface. Repair as needed.
    15.4 EXPANSION JOINTS
    15.5 SKIMMER(S)
    15.6 LADDER(S)
    15.7 STAIRS / RAILS
    15.8 DIVING BOARD
    15.9 SLIDES
    15.10 IN-POOL LIGHTING
    15.11 ELECTRIC / GFCI
    15.12 HEATER
    15.13 GAS / FUEL LINES
    15.14 PUMP / MOTOR(S)
Normal wear.


Air is leaking into the pump gaskets.  Recommend general repair.

    15.15 FILTER SHELL
Normal wear.
    15.16 PIPING / VALVES
Pop up cleaners and water filler systems need occasional service.  Service as needed.

Pop up cleaners are not working properly.  Needs general service.

The automatic filler piping is corroded.  Repair as needed.

    15.17 CHEMICAL FEEDER

Proper water treatment is required to minimize water quality/health hazard concerns including those related to bacteria buildup in components. Children, pregnant women or individuals who are under the influence of alcohol or drugs, medicinal or otherwise, should not use a spa or hot tub. Manufacturer's guidelines on use, cleaning, water temperatures, and operation should be reviewed and followed.



Recommend periodic service of electric water purification system.
    15.18 CONTROL CONDITION
Normal wear.  Controls are hard to access due to the brick isolation wall.
    15.19 FENCING / GATES
There is direct access to the pool from the house.
S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
15.16 PIPING / VALVES Picture 1
15.16 PIPING / VALVES Picture 2
15.17 CHEMICAL FEEDER Picture 1
NOTE: Obtain information on pool design and operation from the owner and service company. Follow the manufacturer's pool use and maintenance guidelines. All patios or other surfaces around the pool should be maintained to allow for water drainage and to prevent slip/trip hazards. Check all components regularly for defects or other detrimental conditions. A properly working Ground-fault Circuit-interrupter (GFCI) should be provided on pool circuits. A qualified electrician should check pool grounding and bonding provisions. Proper water treatment is required to minimize water quality concerns and health hazards. Fencing or other suitable barriers are required are recommended to help prevent unauthorized use. The installation of self-closing/self-latching child-resistant gates and water entry alarms is also advised when children may be present. Be aware; however, that neither fencing nor other devices are substitutes for the proper supervision of children. Check with local authorities for requirements. A qualified pool service company should perform pool repair or servicing work, including seasonal startup and shutdown.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Pool/Spa - Evaluation of all pool elements is limited to the visible condition of components above ground or water level. Evaluation for structural damage and/or leakage is not possible without continual observation and/or drainage. Electrical ground continuity, the chemical composition of the water, and internal filter condition were also not determined. Obtain information on system design and operation from the owner and service company. For a detailed assessment of the pool's history of service and condition, contact the service company that installed/serviced the pool.
Fencing/Gates - Fencing is required for most pools. The use of self-closing/self-latching child-resistant gates and entry/water alarms is also advised. Check with local requirements or recommendations on pool gates/fencing. (Note: Barriers are supplements to supervision, not substitutes for it.)
Filtration System - Comments on the filtration system are generally limited to assessment of external appearances. Adequacy, efficiency, etc., are not addressed. Routine servicing is advised.
Tilework/Grouting - While damage may be readily apparent in only a few areas, all tiled areas should be checked whenever grout, coping or other edging material repair is needed. The expansion joint around in-ground pools should be kept sealed with a suitable grout or expandable compound.
Pool Lights - Grounding provisions for pool lights/components must be assessed by an electrician. Any work related to pool electric or lighting should only be performed by a qualified specialist. Only the appropriately labeled fixtures should be used and professionally installed.
Electric/GFCI - Electric deficiencies should be attended to immediately. A properly working Ground-Fault Circuit-Interrupter (GFCI) should be provided on pool lighting and electric circuits, particularly if within 5-10 feet of the pool.
Maintenance/Service - Pool repairs/services should be performed by a qualified pool service company. Review operating and maintenance requirements with the service technician.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
Report ID# Sample Report / Client
Lawn sprinkler (irrigation) system inspections are not part of a standard home inspection. When provided as an ancillary service, the inspection of lawn sprinkler (irrigation) systems is limited to readily visible and accessible elements as listed herein. The inspection does include a pressure test of piping integrity, assessment of water/content effects on the building and/or site elements, the operation of timing devices and other controls, test of backflow preventers, or evaluation of systems efficiency and effectiveness.

DESCRIPTION:
In-Ground
ESTIMATED ZONES:
3-4
APPROXIMATE AREAS SERVICED:
All Sides
OPERATION:
Manual
Automatic
WATER SUPPLY:
Backflow Preventer
House Line
SPECIAL LIMITATIONS:
Vegetation
SFPNANI 
    16.0 SPRAY HEADS
Not all drip heads are visible due to landscape.
    16.1 COVERAGE PROVISIONS
Expect normal adjustments as the seasons change.
    16.2 EXPOSED PIPING
Most piping is buried, preventing direct inspection.
    16.3 CONTROL PANEL
Valves show typical leakage. Repair as needed. Most valves are buried in wet conditions. Anticipate periodic servicing.

The backyard valves are covered in water and may be leaking. Repair.

The control panel was not accessible due to a missing key. Recommend further evaluation when programming.  Valves were only operated in a manual test mode.  Electronic valve activation should be checked and maintained.

S=Satisfactory, F=Fair, P=Poor/Defective, NA=Not Applicable, NI=Not Inspected
Review REPORT TERMINOLOGY on Introduction Page. Consult with your Inspector for clarification on ratings or findings if there are any questions.
16.3 CONTROL PANEL Picture 1
16.3 CONTROL PANEL Picture 2
16.3 CONTROL PANEL Picture 3
NOTE: Irrigation systems require regular maintenance. A qualified irrigation system specialist should pressure check the system, perform seasonal startup and shutdown, and complete repairs when needed.

SUPPLEMENTAL INFORMATION - Review the additional details below.
Inspection Limitations - A lawn sprinkler inspection is limited to a check of the visible components. No analyses of possible underground leakage, the affect of water  content on the building and/or site elements, or overall efficiency were performed. In some areas the mineral contents of the water may cause staining of exterior components. A service company should be contacted if full evaluation of the system is desired or required.
Maintenance/Service -  A qualified irrigation specialist is recommended for service, winterization, seasonal startup, or if deficiencies exist.
Electric Components - All wiring should be protected from physical damage and maintained in covered watertight junction boxes. Ground-Fault Circuit Interrupters are recommended.
Automatic Controls - The presence of automatic controls may have prevented or at least limited evaluation of the system. Advise review of operation with owner and/or qualified service person.
Sprinkler Head Conditions - Minor sprinkler head damage is typically a maintenance item; however, if a malfunction occurs, the possibility of water supply concerns or concealed defects must be considered.

(c) Copyright 2001-2008 DBR Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom
 
Report ID: Sample Report / Client
SUMMARY OF INSPECTOR COMMENTS

This Summary of Inspector Comments is only one section of the Inspection Report and is provided for guidance purposes only. This Summary is NOT A HOME INSPECTION REPORT and does not include information on all conditions or concerns associated with this home or property. The Inspection Report includes more detailed information on element ratings/conditions and associated information and must be read and considered in its entirety prior to making any conclusive purchase decisions or taking any other action. Any questionable issues should be discussed with the Inspector and/or Inspection Company.

Note: While listings in this Summary of Inspector Comments may serve as a guide to help prioritize remedial needs, the final decision regarding any action to be taken must be made by the client following consultation with the appropriate specialists or contractors.

1.  ROOFING
1.1   ROOF COVERING 2  
  Fair  
Normal wear noted for age.

2.  EXTERIOR ELEMENTS
2.0   SIDING and Flashing  
  Fair  
Noted typical stucco cracks at door and window opening.  There are several drill holes and gouges that need general repair.  Repair as needed.

The pest control application cover needs to be securely attached. Recommend further review of treatment history.

2.6   FOUNDATION COATING  
  Fair  
Recommend trimming back vegetation in contact with the house.

Not all foundation is visible due to stucco built into the grade.
2.8   EXTERIOR FAUCET(S)  
  Fair  
Noted typical leakage from valve stem.  Repair as needed.

A backflow preventer/anti-siphon device is generally required for exterior faucets and lawn irrigation systems in this area to prevent possible contamination of the water supply condition. Add where needed.

Noted corrosion at the rear pool back flow preventer.  Repair as needed.(Picture 1)


3.  SITE ELEMENTS
3.0   PATIO(S) and columns  
  Fair  
Noted sheetrock tape joints loosening in the ceiling. Repair as needed.
3.5   SITE GRADING and vegetation  
  Fair  
Keep vegetation clear of the siding and stem wall.

There are uneven areas in the backyard from missing plants. Recommend leveling to prevent tripping.


4.  GARAGE/CARPORT
4.7   VEHICLE DOOR(S)  
  Fair  
Recommend lubrication ... Noted noisy hinges.
4.8   DOOR OPERATOR(S) and safety reverse  
  Fair  
Normal wear.

Needs lubrication and service.

6.  BATHROOMS
6.0   SINK(S)------------------------------------------------BATHROOM ONE  
  Fair  
Shut off valves are stiff.  Use caution if you need to turn.

Hot water heater is turned off.  Could not verify hot water supply.  Recommend verifying hot water prior to closing.
6.2   BATHTUB  
  Fair  
Hot water is not on.  Recommend further review when the water heater is functioning.
6.3   STALL SHOWER  
  Fair  
Hot water is not on.  Recommend further review when the water heater is functioning.
6.9   SINK(S)---------------------------------------------------------BATHROOM TWO  
  Fair  
Shut off valves are stiff.  Use caution if you need to turn.

Hot water heater is turned off.  Could not verify hot water supply.  Recommend verifying hot water prior to closing.
6.11   BATHTUB  
  Fair  
Normal wear.

Hot water heater is turned off.  Could not verify hot water supply.  Recommend verifying hot water prior to closing.

7.  KITCHEN
7.0   PLUMBING / SINK  
  Fair  
Shut-off valves are stiff.

RO Water purifier should be serviced periodically.

Hot water is not on.  Recommend further review when the water heater is functioning.

7.5   MICROWAVE  
  Fair  
Normal wear.
7.6   DISHWASHER  
  Fair  
Normal wear.
7.7   DISPOSAL  
  Poor/Defective  
Disposal did not operate; Repair.
7.8   VENTILATOR  
  Fair  
Recommend sealing air leakage.  Much of the vented air is leaking back into the kitchen.  There may be something blocking the air flow to the installed ducting.  Repair.

8.  INTERIOR ELEMENTS
8.7   SLIDER/PATIO DOORS  
  Fair  
Screen door latch needs repair.

9.  FOUNDATION / SLAB
9.0   SLAB EXTERIOR / EDGE  
  Fair  
Not all foundation is visible due to landscape rock covering the stem wall.

Noted areas where vegetation covers the siding. Repair as needed.

10.  ELECTRIC SYSTEM
10.5   DEVICES  
  Fair  
The middle switch at the patio door needs repair to operate properly.

Outdoor outlet cover needs repair.


11.  COOLING SYSTEM
11.0   COOLING SYSTEM--COOLING SYSTEM 1  
  Fair  
27.6 RLA 82-64=18 deg temp diff.  Recommend annual service to maintain performance.  Normal readings should be between 16  to 24 deg temp diff..
11.1   OUTDOOR UNIT WITH SAFETY SHUT OFFS  
  Fair  
Weather worn.

Recommend cleaning the coil inside the A/C cabinet periodically due to over grown vegetation.

13.  PLUMBING SYSTEM
13.0   WATER SUPPLY PIPING  
  Fair  
PEX Plastic piping noted in the garage attic area.  Certain types of plastic piping systems have exhibited material or installation deficiencies resulting in premature leakage, particularly polybutylene (PB) piping manufactured prior to the mid 1990s. Some PB piping that developed leaks qualified for a special PB pipe repair program administered by the Consumer Plumbing Recovery Center or other group.  Some other settlement programs were also established.  Any problems that develop in newer systems may qualify for remedial work under manufacturer warranties. Contact the CPRC, the pipe manufacturer, or a qualified plumber or for assessment of the system and possible remedies if any prior concerns were reported or ongoing concerns exist(Picture 4).

Recommend periodic service of water softener system.  Repair corroded connection as needed.(Picture 3)

13.4   EXTERIOR FAUCET(S)  
  Fair  
Noted typical leaking at valve stem.


May need repair at the pool leveler and corroded shut off valve.

A backflow preventer/anti-siphon device is generally required for exterior faucets and lawn irrigation systems in this area to prevent possible contamination of the water supply condition. Add where needed.


14.  HOT WATER SUPPLY
14.0   WATER HEATER SYSTEM 1  
  Not Inspected  
Normal wear. 

Gas is turned off at the control valve. Recommend service company verifying safe operation when gas is turned on.(Picture 2)


15.  POOL
15.2   COPING / EDGING  
  Fair  
Noted mineral deposits which should be cleaned.
15.3   TILEWORK / GROUTING  
  Fair  
Noted mineral build up on the surface. Repair as needed.
15.14   PUMP / MOTOR(S)  
  Fair  
Normal wear.


Air is leaking into the pump gaskets.  Recommend general repair.

15.16   PIPING / VALVES  
  Fair  
Pop up cleaners and water filler systems need occasional service.  Service as needed.

Pop up cleaners are not working properly.  Needs general service.

The automatic filler piping is corroded.  Repair as needed.

15.17   CHEMICAL FEEDER  
  Fair  

Proper water treatment is required to minimize water quality/health hazard concerns including those related to bacteria buildup in components. Children, pregnant women or individuals who are under the influence of alcohol or drugs, medicinal or otherwise, should not use a spa or hot tub. Manufacturer's guidelines on use, cleaning, water temperatures, and operation should be reviewed and followed.



Recommend periodic service of electric water purification system.
15.18   CONTROL CONDITION  
  Fair  
Normal wear.  Controls are hard to access due to the brick isolation wall.
15.19   FENCING / GATES  
  Fair  
There is direct access to the pool from the house.

16.  LAWN SPRINKLER
16.0   SPRAY HEADS  
  Fair  
Not all drip heads are visible due to landscape.
16.1   COVERAGE PROVISIONS  
  Fair  
Expect normal adjustments as the seasons change.
16.2   EXPOSED PIPING  
  Fair  
Most piping is buried, preventing direct inspection.
16.3   CONTROL PANEL  
  Poor/Defective  
Valves show typical leakage. Repair as needed. Most valves are buried in wet conditions. Anticipate periodic servicing.

The backyard valves are covered in water and may be leaking. Repair.

The control panel was not accessible due to a missing key. Recommend further evaluation when programming.  Valves were only operated in a manual test mode.  Electronic valve activation should be checked and maintained.


(c) Copyright 2001-2008 HMA Each HouseMaster Franchise is an Independently Owned and Operated Business.

Prepared Using HomeGauge 4 http://www.HomeGauge 4.com SHGI (c) 2000-2009 : Licensed To Rogers & Kunnen Inc dba HouseMaster Home and Termite Inspections
Top Table of Contents Bottom
 
Report ID: Sample Report / Client
INVOICE
Rogers & Kunnen Inc dba HouseMaster Home and Termite Inspections
3030 S Rural Rd, STE #109
Tempe AZ 85282
480-345-8570
Inspection Date: 8/16/2010
Inspected By: Harold J Kunnen
Customer Info: Inspection Property:
HouseMaster Client
12345 Sample Report
Phoenix AZ xxxxxx
 
ServicePriceAmountSub-Total
Std.Inspection 414.00 1 414.00
Termite 10.00 1 10.00
Water Works Special 95.00 1 95.00

Tax $0.00
Total Price $519.00

Payment Method: Credit Card
Payment Status: Paid by Credit Card in a few days
Notes: Invoice Included in Report Upload

(c) Copyright 2001-2008 HMA Each HouseMaster Franchise is an Independently Owned and Operated Business.
Top Table of Contents Bottom