| Report ID: Sample Report / Client |
| Prepared For: | |
| HouseMaster Client | |
| Property Address: | |
|
12345 Sample Report Phoenix AZ xxxxxx |
|
|
|
| Rogers & Kunnen Inc dba HouseMaster Home and Termite Inspections | |
| Inspector: Harold J Kunnen | |
|
3030 S Rural Rd, STE #109 Tempe AZ 85282 480-345-8570 |
|
| Inspection Date: 8/16/2010 | |
| (c) Copyright 2001-2008 HMA | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
|
|
| Report ID: Sample Report / Client |
|
|
| Inspection Report Attachments |
| HouseMaster on Twitter, Facebook & YouTubeSample Termite Report |
| (c) Copyright 2001-2008 HMA | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
|
|
| Report ID: Sample Report / Client |
| (c) Copyright 2001-2008 HMA | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
|
|||||
| INSPECTION INFORMATION | ||||||||||||||||
|
|
|||||||||||||||
| INSPECTION DETAILS | ||||||||||||||
|
||||||||||||||
| INTRODUCTION |
| The purpose of this report is to render the inspector's professional opinion of the condition of the inspected elements of the referenced property (dwelling or house) on the date of inspection. Such opinions are rendered based on the findings of a standard limited time/scope home inspection performed according to the Terms and Conditions of the Inspection Order Agreement and in a manner consistent with applicable home inspection industry standards. |
| The inspection was limited to the specified, readily visible and accessible installed major structural, mechanical and electrical elements (systems and components) of the house. The inspection does not represent a technically exhaustive evaluation and does not include any engineering, geological, design, environmental, biological, health-related or code compliance evaluations of the house or property. Furthermore, no representations are made with respect to any concealed, latent or future conditions. |
| The GENERAL INSPECTION LIMITATIONS on the following page provides information regarding home inspections, including various limitations and exclusions, as well as some specific information related to this property. |
| The information contained in this report was prepared exclusively for the named Clients and is not transferable without the expressed consent of the Company. The report, including all Addenda, should be reviewed in its entirety. |
| REPORT TERMINOLOGY |
| The following terminology may be used to report conditions observed during the inspection. Additional terms may also be used in the report: |
| SATISFACTORY - Element was functional at the time of inspection. Element was in working or operating order and its condition was at least sufficient for its minimum required function, although routine maintenance may be needed. |
| FAIR - Element was functional at time of inspection but has a probability of requiring repair, replacement or other remedial work at any time due to its age, condition, lack of maintenance or other factors. Have element regularly evaluated and anticipate the need to take action. |
| POOR - Element requires immediate repair, replacement, or other remedial work, or requires evaluation and/or servicing by a qualified specialist. |
| NOT APPLICABLE - All or individual listed elements were not present, were not observed, were outside the scope of the inspection, and/or were not inspected due to other factors, stated or otherwise. |
| NOT INSPECTED (NOT RATED) - Element was disconnected or de-energized, was not readily visible or accessible, presented unusual or unsafe conditions for inspection, was outside scope of the inspection, and/or was not inspected due to other factors, stated or otherwise. Independent inspection(s) may be required to evaluate element conditions. If any condition limited accessibility or otherwise impeded completion of aspects of the inspection, including those listed under LIMITATIONS, it is recommended that limiting factors be removed or eliminated and that an inspection of these elements be arranged and completed prior to closing. |
| IMPORTANT NOTE: All repair needs or recommendations for further evaluation should be addressed prior to closing. It is the client’s responsibility to perform a final inspection to determine the conditions of the dwelling and property at the time of closing. If any decision about the property or its purchase would be affected by any condition or the cost of any required or discretionary remedial work, further evaluation and/or contractor cost quotes should be obtained prior to making any such decisions. |
| NATURE OF THE FRANCHISE RELATIONSHIP |
| The Inspection Company ("Company") providing this inspection report is a franchisee of HMA Franchise Systems, Inc. ("Franchisor"). As a franchisee, the Company is an independently owned and operated business that has a license to use the HouseMaster names, marks, and certain methods. In retaining the Company to perform inspection services, the Client acknowledges that Franchisor does not control this Company’s day-to-day activities, is not involved in performing inspections or other services provided by the Company, and is in no way responsible for the Company’s actions. Questions on any issues or concerns should be directed to the listed Company. |
| GENERAL INSPECTION LIMITATIONS |
| CONSTRUCTION REGULATIONS - Building codes and construction standards vary regionally. A standard home inspection does not include evaluation of a property for compliance with building or health codes, zoning regulations or other local codes or ordinances. No assessments are made regarding acceptability or approval of any element or component by any agency, or compliance with any specific code or standard. Codes are revised on a periodic basis; consequently, existing structures generally do not meet current code standards, nor is such compliance usually required. Any questions regarding code compliance should be addressed to the appropriate local officials. |
| HOME MAINTENANCE - All homes require regular and preventive maintenance to maximize the economic life spans of elements and to minimize unanticipated repair or replacement needs. Annual maintenance costs may run 1 to 3% (or more) of the sales price of a house depending on age, design, and/or the degree of prior maintenance. Every homeowner should develop a preventive maintenance program and budget for normal maintenance and unexpected repair expenses. Remedial work should be performed by a specialist in the appropriate field following local requirements and best practices. |
| ENVIRONMENTAL AND MOLD ISSUES (AND EXCLUSIONS) - The potential health effects from exposure to many elements found in building materials or in the air, soil, water in and/or around any house are varied. A home inspection does not include the detection, identification or analysis of any such element or related concerns such as, but not limited to, mold, allergens, radon, formaldehyde, asbestos, lead, electromagnetic fields, carbon monoxide, insecticides, refrigerants, and fuel oils. Furthermore, no evaluations are performed to determine the effectiveness of any system designed to prevent or remove any elements (e.g., water filters or radon mitigation). An environmental health specialist should be contacted for evaluation of any potential health or environmental concerns. Review additional information on MOLD/MICROBIAL ELEMENTS below. |
| AESTHETIC CONSIDERATIONS - A standard building inspection does not include a determination of all potential concerns or conditions that may be present or occur in the future including aesthetic/cosmetic considerations or issues (appearances, surface flaws, finishes, furnishings, odors, etc.). |
| DESIGN AND ADEQUACY ISSUES - A standard home inspection does not include any element design or adequacy evaluations including seismic or high-wind concerns, soil bearing, energy efficiencies, or energy conservation measures. It also does not address in any way the function or suitability of floor plans or other design features. Furthermore, no determinations are made regarding product defects notices, safety recalls, or other similar manufacturer or public/private agency warnings related to any material or element that may be present in any house or on any property. |
| ESTIMATED AGES - Any age estimations represent the inspector's opinion as to the approximate age, and are provided for general guidance purposes only. Estimations may be based on numerous factors including, but not limited to, appearance and owner comment. Obtain independent verification if knowledge of the specific age of any element is desired or required. Age estimates are given in "years" unless noted. |
| DESIGN LIFE RANGE - These figures represent the typical economic service life range (in years) for elements of similar design, quality and type, as measured from the time of original construction or installation. Any stated design life is presented solely as a guide. It does not take into consideration abnormal, unknown, or discretionary factors, and is not a prediction of future service life. |
| ELEMENT DESCRIPTIONS - Any descriptions or representations of element material, type, design, size, dimensions, etc., are based primarily on visual observation of inspected or representative components. Owner comment, element labeling, listing data, and rudimentary measurements may also be considered in an effort to describe an element. However, there is no guarantee of the accuracy of any material or product descriptions listed in this report; other or additional materials may be present. Independent evaluations and/or testing should be arranged if verification of any element's makeup, design, or dimension is needed. Any questions arising from the use of any particular terminology or nomenclature in this report should be addressed prior to closing. |
| REMEDIAL WORK - Quotes should be obtained prior to closing from qualified (knowledgeable and licensed as required) specialists/contractors to determine actual repair/replacement costs for any element or condition requiring attention. Any cost estimates provided with a home inspection, whether oral or written, only represent an approximation of possible costs. Cost estimates do not reflect all possible remedial needs or costs for the property; latent concerns or consequential damage may exist. If the need for remedial work develops or is uncovered after the inspection, prior to performing any repairs contact the Inspection Company to arrange a re-inspection to assess conditions Aside from basic maintenance suitable for the average homeowner, all repairs or other remedial work should be performed by a specialist in the appropriate field following local requirements and best practices. |
| SELLER DISCLOSURE - This report is not a substitute for Seller Disclosure. A Property History Questionnaire form may be provided with this report to help obtain background information on the property in the event a full Seller Disclosure form is not available. The buyer should review this form and/or the Seller Disclosure with the owner prior to closing for clarification or resolution of any questionable items. A final buyer inspection of the house (prior to or at the time of closing) is also recommended. |
| WOOD-DESTROYING INSECTS/ORGANISMS - In areas subject to wood-destroying insect activity, it is advisable to obtain a current wood-destroying insect and organism report on the property from a qualified specialist, whether or not it is required by a lender. A standard home inspection does not include evaluation of the nature or status of any insect infestation, treatment, or hidden damage, nor does it cover issues related to other house pests or nuisances or subsequent damage. |
| ELEMENTS NOT INSPECTED - Any element or component not evaluated as part of this inspection should be inspected prior to closing. Either make arrangements with the appropriate tradesman or contact the Inspection Company to arrange an inspection when all elements are ready for inspection. |
| HOUSE ORIENTATION - Location descriptions/references are provided for general guidance only and represent orientations based on a view facing the front of the house from the outside. Any references using compass bearings are only approximations. If there are any questions, obtain clarification prior to closing. |
| CONDOMINIUMS - The Inspection of condominium/cooperative do not include exteriors/ typical common elements, unless otherwise noted. Contact the association/management for information on common element conditions, deeds, and maintenance responsibilities. |
| MOLD AND MICROBIAL ELEMENTS / EXCLUSIONS |
| The purpose and scope of a standard home inspection does not include the detection, identification or assessment of fungi and other biological contaminants, such as molds, mildew, wood-destroying fungi (decay), bacteria, viruses, pollens, animal dander, pet or vermin excretions, dust mites and other insects. These elements contain/carry microbial particles that can be allergenic, infectious or toxic to humans, especially individuals with asthma and other respiratory conditions or sensitivity to chemical or biological contaminants. Wood-destroying fungi, some molds, and other contaminants can also cause property damage. One particular biological contamination concern is mold. Molds are present everywhere. Any type of water leakage, moisture condition or moisture-related damage that exists over a period of time can lead to the growth of potentially harmful mold(s). The longer the condition(s) exists, the greater the probability of mold growth. There are many different types of molds; most molds do not create a health hazard, but others are toxic. |
| Indoor mold represents the greatest concern as it can affect air quality and the health of individuals exposed to it. Mold can be found in almost all homes. Factors such as the type of construction materials and methods, occupant lifestyles, and the amount of attention given to house maintenance also contribute to the potential for molds. Indoor mold contamination begins when spores produced by mold spread by air movement or other means to an area conducive to mold growth. Mold spores can be found in the air, carpeting, insulation, walls and ceilings of all buildings. But mold spores only develop into an active mold growth when exposed to moisture. The sources of moisture in a house are numerous and include water leakage or seepage from plumbing fixtures, appliances, roof openings, construction defects (e.g., EIFS wall coverings or missing flashing) and natural catastrophes like floods or hurricanes. Excessive humidity or condensation caused by faulty fuel-burning equipment, improper venting systems, and/or inadequate ventilation provisions are other sources of indoor moisture. By controlling leakage, humidity and indoor air quality, the potential for mold contamination can be reduced. To prevent the spread of mold, immediate remediation of any water leakage or moisture problems is critical. For information on mold testing or assessments, contact a qualified mold specialist. |
| Neither the evaluation of the presence or potential for mold growth, nor the identification of specific molds and their effects, fall within the scope of a standard home inspection. Accordingly, the Inspection Company assumes no responsibility or liability related to the discovery or presence of any molds, their removal, or the consequences whether property or health-related. |
| ADDITIONAL COMMENTS |
|
Mechanical System Upgrade Needs - No evaluations are made as part of a standard home inspection regarding heating, ventilation, or air conditioning (HVAC) system design, system efficiency, adequacy, compliance with current energy standards or costs, and other factors that may be associated with the need to or desire to repair, replace, or upgrade any equipment. If new HVAC equipment is required or desired, now or in the future, in addition to costs associated with the purchase and installation of the equipment itself, there may be additional expenses related to structural alteration or air handler and distribution system replacement or alterations. For additional information on energy efficiency requirements contact ( www.doe.gov). Pictures in Report - Any pictures (photographs, graphics, or images) included in or provided in conjunction with this Inspection Report generally portray overviews of certain elements, depict specific conditions or defects described in report comments, or are used for orientation purposes. Pictures provided do not necessarily reflect all conditions or issues that need attention or may otherwise be a concern. The inclusion of any picture is not in anyway designed to highlight or diminish the significance or severity of any defect or condition, except as may be described in the Inspection Report. The report must be read in its entirety for pertinent information. The inspection is being conducted in accordance with the STANDARDS OF PROFESSIONAL PRACTICE For Arizona Home Inspectors. Cick to Review the AZ SOPP |
| (c) Copyright 2001 - 2008 HMA | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
ROOF COVERING 1: Type: Steep Slope Material: Concrete Tile Location: House and Garage Est. Age: 6 Years Design Life: 40-60 Years Insp. Method: Walked Special Limitations: Roof Design and/or Height | ROOF COVERING 2: Type: Flat/Minimal Slope Material: Single Ply Location: Rear Est. Age: 6 Years Design Life: 5-10 Years Insp. Method: Walked | CHIMNEY 1: N/A |
| S | F | P | NA | NI | ||
![]() | 1.0 | ROOF COVERING 1 Tile mortar is cracking. Repair as needed Trees should be trimmed away from the house to prevent damage. |
||||
![]() | 1.1 | ROOF COVERING 2 Normal wear noted for age. |
||||
![]() | 1.2 | EXPOSED FLASHING | ||||
![]() | 1.3 | PLUMBING STACKS | ||||
![]() | 1.4 | VENTILATION COVERS | ||||
![]() | 1.5 | SKYLIGHT(S) | ||||
![]() | 1.6 | RAIN GUTTERS / EAVESTROUGHS | ||||
![]() | 1.7 | DOWNSPOUTS / ROOF DRAINS | ||||
![]() | 1.8 | FASCIA / SOFFITS | ||||
![]() | 1.9 | CHIMNEY | ||||
| S | F | P | NA | NI | ||
![]() | ![]() |
![]() | ![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
SIDING: Stucco | PORCHES/DECKS: N/A | SPECIAL LIMITATIONS: Vegetation Overgrowth |
| S | F | P | NA | NI | ||
![]() | 2.0 | SIDING and Flashing Noted typical stucco cracks at door and window opening. There are several drill holes and gouges that need general repair. Repair as needed. The pest control application cover needs to be securely attached. Recommend further review of treatment history. |
||||
![]() | 2.1 | WINDOWS | ||||
![]() | 2.2 | ENTRY DOORS | ||||
![]() | 2.3 | STAIRS / STOOPS | ||||
![]() | 2.4 | PORCH(ES) | ||||
![]() | 2.5 | RAILINGS | ||||
![]() | 2.6 | FOUNDATION COATING Recommend trimming back vegetation in contact with the house. Not all foundation is visible due to stucco built into the grade. |
||||
![]() | 2.7 | ELECTRIC / GFCI | ||||
![]() | 2.8 | EXTERIOR FAUCET(S) Noted typical leakage from valve stem. Repair as needed. A backflow preventer/anti-siphon device is generally required for exterior faucets and lawn irrigation systems in this area to prevent possible contamination of the water supply condition. Add where needed. Noted corrosion at the rear pool back flow preventer. Repair as needed.(Picture 1) |
||||
| S | F | P | NA | NI | ||
![]() | ![]() |
![]() | ![]() |
![]() | ![]() |
![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
PATIOS and columns: Type: Concrete Enclosure: Roof Only Location: Rear of House Column type: Stucco over wood frame | WALKWAYS/DRIVEWAYS: Walks: Concrete Driveway: Concrete | RETAINING WALLS: N/A |
SPECIAL LIMITATIONS: Vegetation |
| S | F | P | NA | NI | ||
![]() | 3.0 | PATIO(S) and columns Noted sheetrock tape joints loosening in the ceiling. Repair as needed. |
||||
![]() | 3.1 | WALKWAYS | ||||
![]() | 3.2 | DRIVEWAY | ||||
![]() | 3.3 | RETAINING WALL(S) | ||||
![]() | 3.4 | GROUND SLOPE AT FOUNDATION | ||||
![]() | 3.5 | SITE GRADING and vegetation Keep vegetation clear of the siding and stem wall. There are uneven areas in the backyard from missing plants. Recommend leveling to prevent tripping. |
||||
| S | F | P | NA | NI | ||
![]() | ![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
GARAGE DESCRIPTION and fire separation: Type: Two Car Construction: Wood Frame Finish at House: Drywall on Wall Door at House: Solid Door w/ Self-closer | GARAGE ROOF: Type: Moderate Slope Material: Concrete Tile Est. Age: 6 Years Design Life: 40-60 Years Insp. Method: Walked Special Limitations: Roof Design and/or Height | GARAGE ATTIC: Insp. Method: Limited Entry Form: Indeterminate Type: None |
HOUSE/GARAGE WALL: Finish at House: Drywall on Wall Door at House: Solid Door w/ Self-closer Insulation: Indeterminate - Wall Covered Vapor Retarder: Indeterminate | SPECIAL LIMITATIONS: Covered Framing |
| S | F | P | NA | NI | ||
![]() | 4.0 | ROOFING Refer to roofing section. |
||||
![]() | 4.1 | EXPOSED FRAMING Framing is covered. |
||||
![]() | 4.2 | FLOOR SLAB THe slab is labeled post tension concrete. Do not drill holes. |
||||
![]() | 4.3 | FOUNDATION Not all foundation is visible due to storage and cabinets. |
||||
![]() | 4.4 | ATTIC VENTILATION | ||||
![]() | 4.5 | WALLS / CEILINGS Typical wear. |
||||
![]() | 4.6 | SIDING Normal Wear |
||||
![]() | 4.7 | VEHICLE DOOR(S) Recommend lubrication ... Noted noisy hinges. |
||||
![]() | 4.8 | DOOR OPERATOR(S) and safety reverse Normal wear. Needs lubrication and service. |
||||
![]() | 4.9 | ELECTRIC / GFCI | ||||
![]() | 4.10 | HOUSE / SERVICE DOOR(S) | ||||
| S | F | P | NA | NI | ||
![]() | ![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
ATTIC: Style: Indeterminate Insp. Method: Inaccessible | ROOF CONSTRUCTION: Framing: Wood Trusses Deck: Wood Sheathing Deck: Plywood | INSULATION: Form: Indeterminate Form: Blankett/Batt Type: Fiberglass Est. Average: 8+/- Inches Vapor Retarder: Oberved in Areas/Extent Indeterminate |
VENTILATION PROVISIONS: Location: Rooftop | SPECIAL LIMITATIONS: No Access |
| S | F | P | NA | NI | ||
![]() | 5.0 | ROOF FRAMING There is no access to inspect attic space. |
||||
![]() | 5.1 | ROOF DECK / SHEATHING | ||||
![]() | 5.2 | VENTILATION PROVISIONS | ||||
![]() | 5.3 | ATTIC VENTILATOR(S) | ||||
![]() | 5.4 | WHOLE HOUSE FAN | ||||
![]() | 5.5 | INSULATION No access on the cathedral attic area of the house. |
||||
![]() | 5.6 | ATTIC STAIRS | ||||
| S | F | P | NA | NI | ||
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
BATHROOM ONE: Description: Master Bath Location: Master Bedroom Ventilator(s): Exhaust Fan | BATHROOM TWO: Description: Full Bath Location: Hallway Ventilator(s): Exhaust Fan | SPECIAL LIMITATIONS: Hot Water is Off |
| S | F | P | NA | NI | ||
![]() | 6.0 | SINK(S)------------------------------------------------BATHROOM ONE Shut off valves are stiff. Use caution if you need to turn. Hot water heater is turned off. Could not verify hot water supply. Recommend verifying hot water prior to closing. |
||||
![]() | 6.1 | TOILET | ||||
![]() | 6.2 | BATHTUB Hot water is not on. Recommend further review when the water heater is functioning. |
||||
![]() | 6.3 | STALL SHOWER Hot water is not on. Recommend further review when the water heater is functioning. |
||||
![]() | 6.4 | SURROUND / ENCLOSURE | ||||
![]() | 6.5 | FLOOR(ING) | ||||
![]() | 6.6 | WALLS / CEILING | ||||
![]() | 6.7 | VENTILATOR | ||||
![]() | 6.8 | ELECTRIC / GFCI | ||||
![]() | 6.9 | SINK(S)---------------------------------------------------------BATHROOM TWO Shut off valves are stiff. Use caution if you need to turn. Hot water heater is turned off. Could not verify hot water supply. Recommend verifying hot water prior to closing. |
||||
![]() | 6.10 | TOILET | ||||
![]() | 6.11 | BATHTUB Normal wear. Hot water heater is turned off. Could not verify hot water supply. Recommend verifying hot water prior to closing. |
||||
![]() | 6.12 | STALL SHOWER | ||||
![]() | 6.13 | FLOOR(ING) | ||||
![]() | 6.14 | WALLS / CEILING | ||||
![]() | 6.15 | VENTILATOR | ||||
![]() | 6.16 | ELECTRIC / GFCI | ||||
| S | F | P | NA | NI | ||
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
![]() |
RANGE: Electric Range Estimated Age: 6 Years | DISHWASHER: Estimated Age: 6 Years | DISPOSAL: Estimated Age: 6 Years |
VENTILATOR: Exhaust Fan Integral w/ Microwave |
| S | F | P | NA | NI | ||
![]() | 7.0 | PLUMBING / SINK Shut-off valves are stiff. RO Water purifier should be serviced periodically. Hot water is not on. Recommend further review when the water heater is functioning. |
||||
![]() | 7.1 | FLOOR | ||||
![]() | 7.2 | WALLS / CEILING | ||||
![]() | 7.3 | ELECTRIC / GFCI | ||||
![]() | 7.4 | RANGE Normal wear. |
||||
![]() | 7.5 | MICROWAVE Normal wear. |
||||
![]() | 7.6 | DISHWASHER Normal wear. |
||||
![]() | 7.7 | DISPOSAL Disposal did not operate; Repair. |
||||
![]() | 7.8 | VENTILATOR Recommend sealing air leakage. Much of the vented air is leaking back into the kitchen. There may be something blocking the air flow to the installed ducting. Repair. |
||||
![]() | 7.9 | CABINETRY | ||||
![]() | 7.10 | COUNTERTOP | ||||
| S | F | P | NA | NI | ||
![]() | ![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
PREDOMINANT WALLS & CEILINGS: Wood Frame w/ Drywall | PREDOMINANT FLOORS: Concrete Slab w/ Carpeting and Tile | PREDOMINANT WINDOWS: Sliders w/Insulated Glass w/Screens |
FIREPLACES/STOVES: N/A | DETECTORS: Location: Hallway/Sleeping Area Type: Battery Operated Type: Hard-Wired |
| S | F | P | NA | NI | ||
![]() | 8.0 | CEILINGS Normal wear. |
||||
![]() | 8.1 | WALLS Normal wear. Needs minor painting touchups. |
||||
![]() | 8.2 | FLOORS (SLAB) Covered areas are indirectly inspected. |
||||
![]() | 8.3 | STAIRS | ||||
![]() | 8.4 | RAILINGS | ||||
![]() | 8.5 | WINDOWS Normal wear. Some windows are dirty. Recommend further evaluation. |
||||
![]() | 8.6 | ROOM DOORS | ||||
![]() | 8.7 | SLIDER/PATIO DOORS Screen door latch needs repair. |
||||
![]() | 8.8 | DETECTOR TEST | ||||
![]() | 8.9 | FIREPLACE | ||||
![]() | 8.10 | FIREPLACE GAS BURNERS | ||||
| S | F | P | NA | NI | ||
![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
The inspection of the house foundation/slab is limited to readily visible and access elements as listed herein. Most areas of a concrete house slabs are concealed from view due to foundation plantings, finished walls, high exterior grade lines, floor coverings, furnishings and other elements, and therefore cannot be inspected. Comments provided in this section only apply to the house slab; basement and garage slabs are typically covered in the respective report sections. Neither the inspection nor report includes geological surveys, soil compaction studies, ground testing, evaluation of the effects of or potential for earth movement such as earthquakes, landslides, or sinking, rising or shifting for any reason, or determination of prior flooding or water penetration. Furthermore, a standard home inspection is not a wood-destroying insect inspection, an engineering evaluation, a design analysis, or a structural adequacy study, including that related to high-wind or seismic restraint requirements.
FLOOR SLAB DESCRIPTION: Whole House Post-Tension Slab | SPECIAL LIMITATIONS: Completely Covered by Floor Covering Completely Covered by Tile/Carpeting |
| S | F | P | NA | NI | ||
![]() | 9.0 | SLAB EXTERIOR / EDGE Not all foundation is visible due to landscape rock covering the stem wall. Noted areas where vegetation covers the siding. Repair as needed. |
||||
![]() | 9.1 | HOUSE FLOOR SLAB Areas could not be observed to report on conditions due to floor coverings, furnishings, or other obstructions. |
||||
| S | F | P | NA | NI | ||
![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
![]() | ![]() |
HOUSE SERVICE: Service Line: Underground Est. Service Capacity: 120/240 Volts; 200 Amps Type Service Feeder: Copper Est. Feeder Capacity: 200 Amps | SERVICE PANEL: Type: Circuit Breaker Main Disconnect: 200 Amps Location: Exterior | DISTRIBUTION PANEL: Type: Circuit Breaker Panel Est. Capacity: 200 Amps Main Disconnect: 200 Amps Location: Exterior |
SUBPANEL: Type: Circuit Breaker Panel Est. Capacity: 40 Amps Location: Pool Equipment | PANEL CIRCUITS: 120 Volt Circuits: Copper Wire 240 Volt Circuits: Copper & Aluminum | CIRCUIT-INTERRUPTERS: GFCI: In Panel GFCI: At Receptacle Outlets AFCI: Two Units Noted in Panel |
SPECIAL LIMITATIONS: Power Was Switched OFF/ON At The Main Disconnect |
| S | F | P | NA | NI | ||
![]() | 10.0 | SERVICE / ENTRANCE LINE | ||||
![]() | 10.1 | SERVICE GROUNDING PROVISIONS | ||||
![]() | 10.2 | MAIN DISCONNECT(S) | ||||
![]() | 10.3 | DISTRIBUTION PANEL | ||||
![]() | 10.4 | SUBPANEL(S) Subpanel box is located at Pool area. |
||||
![]() | 10.5 | DEVICES The middle switch at the patio door needs repair to operate properly. Outdoor outlet cover needs repair. |
||||
![]() | 10.6 | WIRING / CONDUCTORS The wiring for the spa has been partial removed. Recommend further review and repair if a spa is added.(Picture 1) |
||||
![]() | 10.7 | GFCI TEST | ||||
| S | F | P | NA | NI | ||
![]() | ![]() |
![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
![]() | ![]() |
AIR CONDITIONING SYSTEM 1: Brand: Carrier Type: Electric Central Split Est. Age: 6 Years Design Life: 7-10 Years Distribution: Ducted w/ Registers Location: Attic Location: Outside |
| S | F | P | NA | NI | ||
![]() | 11.0 | COOLING SYSTEM--COOLING SYSTEM 1 27.6 RLA 82-64=18 deg temp diff. Recommend annual service to maintain performance. Normal readings should be between 16 to 24 deg temp diff.. |
||||
![]() | 11.1 | OUTDOOR UNIT WITH SAFETY SHUT OFFS Weather worn. Recommend cleaning the coil inside the A/C cabinet periodically due to over grown vegetation. |
||||
![]() | 11.2 | INDOOR BLOWER and Filter | ||||
![]() | 11.3 | CONDENSATE PROVISIONS | ||||
![]() | 11.4 | DUCTWORK and supply vents to each room | ||||
![]() | 11.5 | THERMOSTAT | ||||
| S | F | P | NA | NI | ||
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
![]() |
HEATING SYSTEM 1: Type: Furnace Brand: Carrier Fuel: Natural Gas Location: Attic Est. Age: 6 Years Design Life: 10-15 Years Distribution: Ducted w/ Registers | SPECIAL LIMITATIONS: Power Off/On Vacant House |
| S | F | P | NA | NI | ||
![]() | 12.0 | HEATING UNIT--SYSTEM 1 | ||||
![]() | 12.1 | BURNER | ||||
![]() | 12.2 | FUEL LINE AT UNIT AND SAFETY SHUT OFFS | ||||
![]() | 12.3 | VENT CONNECTOR | ||||
![]() | 12.4 | BLOWER and filters | ||||
![]() | 12.5 | DISTRIBUTION SYSTEM and supply vent to each room | ||||
![]() | 12.6 | THERMOSTAT | ||||
| S | F | P | NA | NI | ||
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
WATER SUPPLY PIPING: Copper Where Visible Cross-linked Poly (PEX) | DRAIN/WASTE LINES: Plastic Plastic (PVC/ABS) | LOCATION OF SHUT-OFFS: Water: At Meter Water: At Left Side of House Gas: At Meter |
WATER TREATMENT SYSTEM: Water Softener | SPECIAL LIMITATIONS: Vacant House |
| S | F | P | NA | NI | ||
![]() | 13.0 | WATER SUPPLY PIPING PEX Plastic piping noted in the garage attic area. Certain types of plastic piping systems have exhibited material or installation deficiencies resulting in premature leakage, particularly polybutylene (PB) piping manufactured prior to the mid 1990s. Some PB piping that developed leaks qualified for a special PB pipe repair program administered by the Consumer Plumbing Recovery Center or other group. Some other settlement programs were also established. Any problems that develop in newer systems may qualify for remedial work under manufacturer warranties. Contact the CPRC, the pipe manufacturer, or a qualified plumber or for assessment of the system and possible remedies if any prior concerns were reported or ongoing concerns exist(Picture 4). Recommend periodic service of water softener system. Repair corroded connection as needed.(Picture 3) |
||||
![]() | 13.1 | WATER FUNCTIONAL FLOW AT FIXTURES | ||||
![]() | 13.2 | DRAIN / WASTE PIPING FUNCTIONAL FLOW | ||||
![]() | 13.3 | FIXTURE DRAINAGE | ||||
![]() | 13.4 | EXTERIOR FAUCET(S) Noted typical leaking at valve stem.
May need repair at the pool leveler and corroded shut off valve. A backflow preventer/anti-siphon device is generally required for exterior faucets and lawn irrigation systems in this area to prevent possible contamination of the water supply condition. Add where needed. |
||||
![]() | 13.5 | LAUNDRY AREA AND VENT FAN and dryer vent Normal wear. The vent fan is installed |
||||
![]() | 13.6 | GAS PIPING Gas shut off is located at the meter. |
||||
| S | F | P | NA | NI | ||
![]() | ![]() |
![]() | ![]() |
![]() | ![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
HOT WATER SUPPLY 1: Type: Direct-heated Tank Brand: Bradford White Est. 5o Gal. Est. Age: 6 Years Design Life: 7-10 Years Location: Garage | SPECIAL LIMITATIONS: Water and Power Turned Off/ON - Vacant House |
| S | F | P | NA | NI | ||
![]() | 14.0 | WATER HEATER SYSTEM 1 Normal wear. Gas is turned off at the control valve. Recommend service company verifying safe operation when gas is turned on.(Picture 2) |
||||
![]() | 14.1 | VENT CONNECTOR | ||||
![]() | 14.2 | GAS / FUEL LINES AT UNIT | ||||
![]() | 14.3 | SAFETY VALVE PROVISIONS | ||||
| S | F | P | NA | NI | ||
![]() | ![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
![]() | ![]() |
DESCRIPTION: In-Ground | LINER/SURFACE: Concrete/Gunite | ESTIMATED AGE: 5 to 10 years |
DESIGN LIFE: 20 to 25 Years | SPECIAL LIMITATIONS: Vegetation |
| S | F | P | NA | NI | ||
![]() | 15.0 | DECK OR PATIO AT POOL | ||||
![]() | 15.1 | INTERIOR FINISH/LINER | ||||
![]() | 15.2 | COPING / EDGING Noted mineral deposits which should be cleaned. |
||||
![]() | 15.3 | TILEWORK / GROUTING Noted mineral build up on the surface. Repair as needed. |
||||
![]() | 15.4 | EXPANSION JOINTS | ||||
![]() | 15.5 | SKIMMER(S) | ||||
![]() | 15.6 | LADDER(S) | ||||
![]() | 15.7 | STAIRS / RAILS | ||||
![]() | 15.8 | DIVING BOARD | ||||
![]() | 15.9 | SLIDES | ||||
![]() | 15.10 | IN-POOL LIGHTING | ||||
![]() | 15.11 | ELECTRIC / GFCI | ||||
![]() | 15.12 | HEATER | ||||
![]() | 15.13 | GAS / FUEL LINES | ||||
![]() | 15.14 | PUMP / MOTOR(S) Normal wear.
Air is leaking into the pump gaskets. Recommend general repair. |
||||
![]() | 15.15 | FILTER SHELL Normal wear. |
||||
![]() | 15.16 | PIPING / VALVES Pop up cleaners and water filler systems need occasional service. Service as needed. Pop up cleaners are not working properly. Needs general service. The automatic filler piping is corroded. Repair as needed. |
||||
![]() | 15.17 | CHEMICAL FEEDER Proper water treatment is required to minimize water quality/health hazard concerns including those related to bacteria buildup in components. Children, pregnant women or individuals who are under the influence of alcohol or drugs, medicinal or otherwise, should not use a spa or hot tub. Manufacturer's guidelines on use, cleaning, water temperatures, and operation should be reviewed and followed. Recommend periodic service of electric water purification system. |
||||
![]() | 15.18 | CONTROL CONDITION Normal wear. Controls are hard to access due to the brick isolation wall. |
||||
![]() | 15.19 | FENCING / GATES There is direct access to the pool from the house. |
||||
| S | F | P | NA | NI | ||
![]() | ![]() |
![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
|
DESCRIPTION: In-Ground | ESTIMATED ZONES: 3-4 | APPROXIMATE AREAS SERVICED: All Sides |
OPERATION: Manual Automatic | WATER SUPPLY: Backflow Preventer House Line | SPECIAL LIMITATIONS: Vegetation |
| S | F | P | NA | NI | ||
![]() | 16.0 | SPRAY HEADS Not all drip heads are visible due to landscape. |
||||
![]() | 16.1 | COVERAGE PROVISIONS Expect normal adjustments as the seasons change. |
||||
![]() | 16.2 | EXPOSED PIPING Most piping is buried, preventing direct inspection. |
||||
![]() | 16.3 | CONTROL PANEL Valves show typical leakage. Repair as needed. Most valves are buried in wet conditions. Anticipate periodic servicing. The backyard valves are covered in water and may be leaking. Repair. The control panel was not accessible due to a missing key. Recommend further evaluation when programming. Valves were only operated in a manual test mode. Electronic valve activation should be checked and maintained. |
||||
| S | F | P | NA | NI | ||
![]() | ![]() |
![]() |
| (c) Copyright 2001-2008 DBR | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
|
|
| Report ID: Sample Report / Client | |
| SUMMARY OF INSPECTOR COMMENTS | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
This Summary of Inspector Comments is only one section of the Inspection Report and is provided for guidance purposes only. This Summary is NOT A HOME INSPECTION REPORT and does not include information on all conditions or concerns associated with this home or property. The Inspection Report includes more detailed information on element ratings/conditions and associated information and must be read and considered in its entirety prior to making any conclusive purchase decisions or taking any other action. Any questionable issues should be discussed with the Inspector and/or Inspection Company.
Note: While listings in this Summary of Inspector Comments may serve as a guide to help prioritize remedial needs, the final decision regarding any action to be taken must be made by the client following consultation with the appropriate specialists or contractors. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| (c) Copyright 2001-2008 HMA | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
|
|
| Report ID: Sample Report / Client |
| INVOICE |
|
Rogers & Kunnen Inc dba HouseMaster Home and Termite Inspections
3030 S Rural Rd, STE #109 Tempe AZ 85282 480-345-8570 |
Inspection Date: 8/16/2010
Inspected By: Harold J Kunnen |
| Customer Info: | Inspection Property: |
|
HouseMaster Client
|
12345 Sample Report Phoenix AZ xxxxxx |
|
||||||||||||||||
|
Tax $0.00 |
||||||||||||||||
| Total Price $519.00 | ||||||||||||||||
Payment Method: Credit Card
Payment Status: Paid by Credit Card in a few days
Notes: Invoice Included in Report Upload
| (c) Copyright 2001-2008 HMA | Each HouseMaster Franchise is an Independently Owned and Operated Business. |